Time Delays; Walk-Through; Pir Sensitivity Adjustment - wattstopper PW-100 Installation Instructions Manual

Passive infrared wall switch occupancy sensor
Hide thumbs Also See for PW-100:
Table of Contents

Advertisement

Presentation Mode
manually turned OFF the PW holds the lights OFF until no motion has been
detected for the duration of the Time Delay. With subsequent occupancy, the PW
turns the load ON. If both relays are ON and one relay is manually turned OFF
this relay remains OFF until both the Time Delay and retrigger delay expires for
the relay that is ON, after that time the ON Mode control settings again apply.

Time Delays

The PW sensor holds the load ON until no motion is detected for the selected
time delay. Select the time delay using DIP switch settings. In the PW-200, both
relays use the same delay.
Test/20 min
(DIP 1, 2, 3, OFF)
Fixed Time Delay
(DIP 1 ON, 2 & 3 OFF)

Walk-Through

The Walk-Through mode shortens the time delay to reduce the amount of time
the load is ON after a brief moment of occupancy, such as returning to an office
to pick up a forgotten item then immediately exiting.
Walk-Through
Mode
(DIP #4 ON)
No Walk-Through
(DIP #4 OFF)

PIR Sensitivity Adjustment

The PW sensor constantly monitors the controlled environment and
automatically adjusts the PIR to avoid common ambient conditions that can
cause false detections, while providing maximum coverage.
High (DIP #5 OFF)
Low, 50%
(DIP #5 ON)
Visit our website for FAQs: www.wattstopper.com
is a feature of the Auto ON mode.When both relays are
A Test Mode with a short time delay of 5 seconds is
set when DIP switches 1, 2, & 3 are OFF. It cancels
automatically after ten minutes, or when you set a
fixed time delay. When the Test Mode times out, the
sensor assumes a 20 minute time delay. To restart
Test Mode, change the time delay setting to any fixed
amount and then return it to the Test setting.
Time delays are 5, 10, 15, 20 (default), 25, or 30
minutes.
The PW sensor turns the load OFF three minutes after
the area is initially occupied, if no motion is detected
after the first 30 seconds. If motion continues beyond
the first 30 seconds, the set time delay applies.
Walk-Through mode disabled.
Default setting. Suitable for most applications.
Reduces sensitivity by approximately 50%. Useful in
cases where the PIR is detecting movement outside of
the desired area (also consider masking the lens) and
where heat sources cause unnecessary activation.