INSTALLATION AND MAINTENANCE INSTRUCTIONS
B401BR Plug-in Detector Base
For use with the following detectors: 1451, 2451, and 2451TH
Specifications
Base Diameter:
Base Height:
Weight:
Mounting:
Operating Temperature Range:
Operating Humidity Range:
Electrical Ratings — includes base and detector
System Voltage:
Maximum Ripple Voltage:
Start-up Capacitance:
Standby Ratings:
Alarm Ratings:
Reset Voltage:
Reset Time:
Start-up Time:
Before Installing
Please thoroughly read the System Sensor manual I56-407,
Guide for Proper Use of System Smoke Detectors, which pro-
vides detailed information on detector spacing, placement,
zoning, wiring, and special applications. Copies of this man-
ual are available at no charge from System Sensor. (For
installations in Canada, refer to CAN4-S524, Standard for the
Installation of Fire Alarm Systems, and CEC Part 1, Sec. 32.)
NOTICE: This manual should be left with the owner/user
of this equipment.
IMPORTANT: The detector used with this base must be
tested and maintained regularly following NFPA 72 require-
ments. The detector used with this base should be cleaned
at least once a year.
D450-02-00
6.2 inches (157 mm) typical
1.1 inches (29 mm) typical
0.3 lb. (130 g) typical
4 inch square box with or without plaster ring. Min. Depth: 1.5 inches
4 inch octagon box. Min. Depth: 1.5 inches
3-1/2 inch octagon box. Min. Depth: 1.5 inches
–10° to 60°C (14° to 140°F)
Note: Do not install where normal ambient temperature extends beyond 0° to 49°
(32° to 120°F)
10% to 93% Relative Humidity
24 VDC
4 Volts peak to peak
0.02 µF Maximum
17 VDC Minimum
32 VDC Maximum
120 µA Maximum
10 mA Minimum at 10.5 VDC
62 mA Maximum at 32 VDC
The optional RA400Z Remote Annunciator operates within the specified detector
alarm currents.
2.50 VDC Minimum
0.3 Sec Maximum
34.0 Sec Maximum
1
General Description
The plug-in detector base B401BR is used with System
Sensor 400 Series photoelectronic, ionization, and heat
detector heads. The ability to accept a variety of detector
heads makes this base more versatile than equivalent
direct-wired models. Refer to the System Sensor catalog for
other available plug-in detector bases.
This B401BR base is intended for use in 2-wire systems,
with screw terminals provided for power, ground, and
remote annunciator connections. The B401BR base also
contains a resistor to provide current limiting in the alarm
state.