14.9 ALARM WINDOW

14.9.1 TRIPPED LOW PRESSURE SWITCH
Fig. 51
POSSIBLE CAUSE 1: EVAPORATOR BLOCKED.
B Clean the evaporator.
B Select Acknowledge.
B Wait until the heat pump starts again.
POSSIBLE CAUSE 2: FAN BLOCKED.
B Remove debris that blocks the fan.
B Select Acknowledge.
B Wait until the heat pump starts again.
POSSIBLE CAUSE 3: REFRIGERANT FAULT IN THE
REFRIGERANT CIRCUIT.
B Check the amount of refrigerant.
B Check the refrigerant circuit for tightness.
B Select Acknowledge.
B Wait until the heat pump starts again.
POSSIBLE CAUSE 4: FAULTY DEFROST SYSTEM OR
FAN MOTOR.
B Check the function of the 4-way valve. Manually
switch the 4-way valve in the corresponding menu
point at the control panel on and off.
B Check the defrost settings.
B Check the fan motor function.
B Select Acknowledge.
B Wait until the heat pump starts again.
POSSIBLE CAUSE 5: EXPANSION VALVE FAULTY.
B Check expansion valve.
B Check for overheating and excessive cooling.
B Select Acknowledge.
B Wait until the heat pump starts again.
14.9.2 TRIPPED HIGH PRESSURE SWITCH
Fig. 52
6 720 641 467 (2010/01)
For latest prices and delivery to your door visit MyTub Ltd - www.mytub.co.uk - info@mytub.co.uk 0844 556 1818
POSSIBLE CAUSE 1: AIR IN THE HEATING SYSTEM.
B Select Acknowledge.
B Check whether air is in the heating system.
B Fill the heating system and vent if required.
POSSIBLE CAUSE 2; BLOCKED PARTICLE FILTER:
B Select Acknowledge.
B Check filter.
6 720 641 467-18.1I
B Clean filter if required ( chapter 14.7).
POSSIBLE CAUSE 3: INADEQUATE FLOW RATE
ACROSS THE HEAT PUMP.
B Select Acknowledge.
B Check whether the heat pump has stopped (
B Check that all the valves are open. The thermostat
B Select a higher speed for the heat transfer medium
Fig. 53 Connection chamber, internal unit
1
2
14.9.3 FAILURE / SHORT CIRCUIT ON SENSOR
Fig. 54
All sensors connected to the heating installation can give
an alarm in the event of a fault. In the example, it is
sensor T3, hot water, which has given an alarm. All
6 720 641 467-19.1I
sensors give alarms in the same way.
ALARM FUNCTIONS AND DISPLAYS
on page 41).
valves in heating systems should be fully open and in
floor heating systems at least half of the coils should
be fully open.
pump (G2). Also set a higher speed for the heating
circuit pump (G1), as it needs to run with a higher
speed than the heat transfer medium pump.
Heating circuit pump, primary
Heating circuit pump, secondary
Fig. 53