Worcester Greensource 9,5 Installation Manual page 23

Air to water heat pump with domestic hot water distribution unit
Table of Contents

Advertisement

8.3.1
EXTERNAL HEAT PUMP CONNECTIONS
Fig. 24 External connections
POWER SUPPLY
Connect the power cable to terminals L1, N and PE
(
chapter 8.4). Ensure connection to the same phase
sequence as the internal unit.
CAN-BUS
Connect the screened communication cable between
the internal unit and the heat pump to terminals GND,
CANL, CANH and 12V (
CAUTION: Do not mix up the 12V and CAN-
BUS connections!
The processors are destroyed if 12V is
connected to the CAN-BUS.
B Check that the four cables are connected
to the contacts with the corresponding
marking on the circuit board.
6 720 641 467 (2010/01)
For latest prices and delivery to your door visit MyTub Ltd - www.mytub.co.uk - info@mytub.co.uk 0844 556 1818
chapter 5.8).
POWER SUPPLY
6 720 641 467-84.1I
23

Advertisement

Table of Contents
loading

This manual is also suitable for:

Greensource 6Greensource 7

Table of Contents