402 is available with a set of Pt500 sensors, either short direct sensors according to EN 1434-2 or D 5.8 mm pocket sensors which fit Kamstrup’s stainless steel sensor pockets. The accumulated heat energy and/or cooling energy can be displayed in kWh, MWh, GJ or in Gcal, all in the form of seven significant digits and a measuring unit.
Cabinet for electronics unit Screws for fitting Fitting. Is also applicable for wall mounting Meter case with holes for cable retainers (cable retainers: 1650-145) Sensor connecting piece and blind plug for short direct sensor Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
2 x 0.25 mm : 2.5 m 2 x 0.25 mm : 10 m 2 x 0.50 mm : 5 m 2 x 0.50 mm : 20 m 2 x 1.00 mm : 10 m Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
® We currently develop new functions and modules for MULTICAL 402. Please contact Kamstrup A/S if your application is not covered by the variants shown. 3.1 Type and programming overview...
402-T only Volumemeter (Hot) Volumemeter (Cold) 402-T only Energymeter Country code (language on label etc.) ® Contact Kamstrup for information on the availability of the above MULTICAL 402 variants on the individual markets. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Page 15
Gaskets for flange meters PN25 glands Size (union) Type no. Size Type no. G¾ 2210-061 DN20 2210-147 2210-062 DN25 2210-133 G5/4 2210-063 DN40 2210-132 2210-065 DN50 2210-099 Contact Kamstrup A/S about further accessories. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Page 17
Number of decimals in display Type CCC No. m³ m³/h Gcal [m³/h] 402-xxxx-xxX-xxx 4-5-7-9 4-5-6-7-8-9 The use of CCC-codes with high resolution reduces the battery lifetime if you choose modules with pulse outputs. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Max. yearly data • 14.3 This year’s min. • 14.4 Min. yearly data • 14.5 This month’s max. • 14.6 Max. monthly data • 14.7 This month’s min. • 14.8 Min. monthly data Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Page 19
Number of yearly data displayed (1…15) Number of monthly data displayed (1…36) DDD=210 is the ”standard code” of heat meters with meter type 402xxxxxxx2xx. Please contact Kamstrup for other combinations. A DDD-code can contain max. 103 readings including 4 data logger counts.
(T1<T2). (Recommended for heat/cooling applications) • • • If P>TL2 energy is saved in TA2 and if Q>TL3 energy is saved in TA3 PQ-tariff See paragraph 7.9 for further details on the tariff registers. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Pulse inputs VA and VB function independently of the meter itself. Therefore their values are not included in any kind of energy calculation. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Page 22
Yearly data, up to latest 15 years • Monthly data, up to latest 36 months By means of METERTOOL counter values VA and VB can be preset to the values of the connected meters at the time of commissioning. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Page 23
Meter no. of VA (max. 8 digits) Yearly data, date of LOG1 (latest target date) Yearly data, value of LOG1 (latest yearly reading) This is the accumulated volume registered on 1 January 2010. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Type 402- Country code Please contact Kamstrup for further details on available country codes. The available country codes appear from internal document 5514-169 on Kamstrup’s Intranet. 3.8.1 Integration time and reset type of info codes ®...
Page 25
® MULTICAL 402 will be supplied with customer label no. 2001-000, which includes the meter’s customer number. Please contact Kamstrup for the creation of new customer labels. 3.8.4 Other functions Creating an order in BOS you can choose ”fixed M-Bus addr” which means that all meters included in the ordre in question will be given the same M-Bus address.
New fibre gaskets in original quality must be used. If other glands than the original ones from Kamstrup A/S are used you must make sure that the threaded lengths of the glands do not prevent proper tightening of the sealing surface.
Page 31
If minimum installation depth (G¾ and G1) is required, The electronics case must not point upwards the flow sensor must be mounted with the electronics case pointing downwards and the calculator on the side Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
G A flow meter should not to be placed after a two-level double bend Figure 10 For general information concerning installation see CEN report DS/CEN/CR 13582, Heat meter Installation. Instructions in selection, installation and use of heat meters. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
® Mounting of glands and short direct sensor mounted in MULTICAL 402 flow part (only G¾ (R½) and G1(R¾)). The short direct sensor from Kamstrup can only be mounted in PN16 installations. The blind plug mounted in the ® MULITCAL 402 flow part can be used in connection with both PN16 and PN25.
Page 34
Figure 14: Wall mounted MULTICAL Figure 15: Fastening of cable If the flow sensor is installed in a humid or condensing environment, the calculator must be mounted higher than the flow sensor. Figure 16 Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
When dimensioning the flow sensor you must take this into consideration, especially if the sensor is used within the scope of EN 1434 between q and q , and in case of heavy contractions of the pipe. Steam pressure [°C] Diagram 3 Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Outlet table k-factor for T1 in (Flow sensor in V1 and flow pipe) Outlet table Cooling meter E3=V1(T2-T1) k-factor for T2 in (Flow sensor in V1 and return pipe) Inlet table Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
402 has been designed for installation indoors in non-condensing environments with ambient temperatures from 5…55°C, however max. 30°C to ensure optimum battery lifetime. Protection class IP54 of calculator and IP65 of flow sensor permits water sprinkling, but the meter does not stand submergence. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Cooling energy: E3 = V1 (T2-T1)k is the heat coefficient of water which is calculated on the basis of the formula stated in prEN 1434-1:2009 (identical with the energy formula of OIML R75-1:2002). Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Page 39
MULTICAL® 402 Kamstrup can supply an energy calculator for check measurement: Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
T1:Forward or T2:Return Cooling energy: E3 = V1(T2-T1)k T1:Forward or T2:Return Flow sensor V1 is placed in flow or return as selected during PROG. (Heat/cooling meter with condensation protection and Pt500 sensor inputs) 402-Txxxxxx6xx Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Page 41
Average of Date of reading Volume forward pipe return pipe 2009.06.01 534.26 m 48236 18654 2008.06.01 236.87 m 20123 7651 28113/297.39 = Yearly 11003/297.39 297.39 m 28113 11003 consumption = 36.99°C 94.53°C Table 7 Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
If you want to switch the qhc function on or off compared to current condition, it is necessary to perform a total programming of the meter by means of METERTOOL. The change between heat and cooling measurement involves no hysteresis (∆θ = 0.00K). θ is configured by means of METERTOOL (see paragraph 14.2). Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
”Reset” sets the max. value to zero and the min. value to e.g. 10000.0 kW at CCC=419. Date of year-to-date max. Value of year-to-date max. Value of this month’s min. Date of this month’s min. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Year-to-date average (since latest target date) • • Month-to-date average (since latest target date) Year-to-date average of T1 (Current date with a stipulated line under year or month is shown immediately BEFORE this reading) Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Heat energy E1 in MWh Yearly data, date of LOG1 (latest yearly reading) Yearly data, value of LOG1 (latest yearly reading) Monthly data, date of LOG1 (latest monthly reading) Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Page 46
As the display is configured according to the customer’s need (selection of DDD-code) the display will usually include much fewer readings than shown in the below diagram. Figure 17 Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Page 47
• • • • • 14.6 Max. monthly data • • • • • • • • 14.7 This month’s min. • • • • • • • • 14.8 Min. monthly data Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Page 48
• • 20.16 M-Bus second. address (N Example of reading of PROG number. A total overview of existing display codes (DDD) is described in a separate document. Please contact Kamstrup for further details. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
The data logger saves the latest 50 changes. The latest 36 changes can be displayed, and the rest can be read by means of METERTOOL. Furthermore, the info code is saved in daily, monthly and yearly logger for diagnostic purposes. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Page 50
This prevents ”infoevent” from counting during transportation and irrelevant data from being saved in the info logger. The first time the meter accumulates the volume register after the installation, the info code automatically becomes active. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
2 tariff conditions TL2 and TL3, which are always used in the same tariff type, are connected to each tariff function. Therefore, it is not possible to “mix” 2 tariff types. Example: EE=11 (Power tariff) TA2 shows energy consumed… …above power limit TL2 (but below TL3) Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Page 52
When either power or flow tariff is used you obtain an overview of the total consumption compared to the part of the consumption used above tariff limit. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Page 53
Setting up data TL3 must always include a higher value than TL2. The return temperature tariff can be used as a basis for weighted user charge. A high return temperature indicates insufficient heat utilization which is uneconomical for the heat supplier. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Page 54
P > TL2 and q > TL3 Accumulation in TA2, TA3 and main register The PQ tariff can e.g. be used for customers who pay a fixed charge based on max. power and max. flow. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
When the info logger is read from the display, the latest 36 changes including dates can be read too. All 50 changes can be read by means of the PC program METERTOOL (paragraph 14). Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
When you press the main key you change to the next digit from right to left: ⇒ The active digit flashes and this digit can be changed by pressing the subkey. You go from the leftmost to the rightmost digit by pressing the main key. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Page 57
Input B (preset of register) Meter no. of Input A Meter no. of Input B Primary M-Bus address Note! Pulse values of Input A and Input B (FF and GG) cannot be changed via the front keys. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Wait a moment without pressing any keys. The legal reading appears and the reset menu is deactivated. Note: If no keys are activated for 4 min., the reset menu is deactivated and the display reverts to legal reading. If the “OK” is not displayed, no data have been saved. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Through the latest 20 years ultrasonic measurement has proved the most long-term stable measuring principle for heat measurement. Both experience from ultrasonic meters in operation and repeated reliability tests carried out in Kamstrup’s accredited long-term test equipment as well as by AGFW in Germany have documented the long- term stability of ultrasonic meters.
Page 60
ASIC. For this purpose a number of absolute time measurements between the two transducers are made. These measurements are subsequently converted into the current velocity of sound, which is used in connection with flow calculations. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
. However, please note that high flow velocities may cause cavitation, especially at low static pressure. See paragraph 6.5 for further details on operating pressure. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
No sensor set Pocket sensor set with 1.5 m cable Pocket sensor set with 3.0 m cable Short direct sensor set with 1.5 m cable Short direct sensor set with 3.0 m cable Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
0.200 25.0 0.040 Table 10 Kamstrup supply Pt500 sensor sets with up to 10 m cable (2 x 0.25 mm 9.3 Installation 9.3.1 Electrical connection The two paired 2-wire sensors must be mounted in terminals 5 and 6 (T1), and 7 and 8 (T2). The polarity of temperature sensors T1 and T2 is unimportant.
Figure 18 Figure 19 The stainless steel pockets can be used for mounting in PN25 systems! Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
The 2 x AA-cell lithium battery is in most applications sufficient to power MULTICAL 402 throughout an operating period of 6 years (see paragraph 10.3). Note: AA-cell lithium batteries include approx. 0.7 g lithium each and are therefore not comprised by transport restrictions. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
402 for up to 16 years (see paragraph 10.4). Note: D-cell lithium batteries include approx. 4.5 g lithium each and are therefore comprised by transport restrictions. See document 5510-408_DK-GB-DE for further details on transportation of lithium batteries. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
National regulations for electric installations must be observed. The 24 VAC module can be connected/disconnected by the heating station’s personnel, whereas the fixed 230/24 V installation in the meter panel must only be carried out by an authorized electrician. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Mains cable, type 5000-286 (2 x 0.75 mm²) ”H05 VV-F” is the designation of a strong PVC mantle, which withstands max. 70°C. Therefore, the mains cable must be installed with sufficient distance to hot pipes etc. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
These tasks can also be carried out by persons or companies, who professionally produce, repair or maintain equipment if only the person carrying out the work has the necessary expert knowledge. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
The pulse outputs are designed with darlington optocouplers, which makes them suitable for most signal types. Please note the polarity when making the connection. See paragraph 2.2 re electrical data of the pulse outputs. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
FF=24 and GG=24 . After delivery the FF and GG codes can be changed by means of the PC program METERTOOL (see paragraph 14) Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
PC connection. The data connection is galvanically isolated by optocouplers, which makes it necessary to use data cable type 66- 99-105 or 66-99-106 in order to adapt the signal to RS232 level which suits a PC or Kamstrup’s hand-held terminal.
Page 78
M-Bus modules. 11.4.6 Wireless M-Bus (Type: 402-0-30 and 402-0-35) (PCB 5550-1029/1203) The Wireless M-Bus module has been designed to form part of Kamstrup’s hand-held Wireless M-Bus Reader system, which operates in the licence-free frequency band in the 868 MHz area.
Page 79
11.4.10 Radio (Type: 402-0-40 and 402-0-41) (PCB 5550-1040) These radio modules are your first choice for reading via Kamstrup’s hand-held reading systems, e.g. USB Meter Reader and hand-held terminal MT Pro, which operate in the licence-free frequency band in the 434 MHz area.
Page 80
11.4.11 Radio (Type: 402-0-42 and 402-0-44) (PCB 5550-1072) The radio modules have been optimized to form part of a Kamstrup radio network system, which operates in the licence-free frequency band in the 434 MHz area, but can also be used for the hand-held reading systems in the same frequency area.
43+45 Switching between NET0 and NET1 via MT Pro. 50+52 Pulse values of VA and VB are changed via METERTOOL. Radio + pulse inputs Switching between NET0 and NET1 via MT Pro. 54+56 Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
The KMP protocol is used in all Kamstrup consumption meters launched from 2006 onwards. The protocol is used for the optical eye and via plug pins for the module area. Thus, modules with e.g. M-bus interface use the KMP protocol internally and the M-bus protocol externally.
Page 83
Utilities and other relevant companies who want to develop their own communication driver for the KMP protocol can order a demonstration program in C# (.net based) as well as a detailed protocol description (in English language). Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
In order to limit the current consumption of the circuit around the IR diode, the circuit is not permanently switched It is activated by either keystroke or communication via the optical eye. The circuit remains switched on for 30 min. after end of communication or after latest keystroke. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Pulse input B/output CV, depending on IO_DEF COM1_TX Serial communication – meter’s TX Ground – 0 volt Not connected Ground – 0 volt TEMP_F Forward temperature, current output TEMP_F1 Forward temperature, power input Ground – 0 volt Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
. Abbreviation Description Flow measurement Temperature measurement Temperature reference measurement Flow calculation Temperature calculation Volume and energy calculation Calculation and integration Normal cycle (24 seconds) Fast/verification cycle (4 seconds) Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Page 87
It is indicated that the meter is in verification mode in that the three dots in the right side of the display flash like in fast mode. At the same time a P for ”test mode” is shown in that of the big 7-segments which is placed farthest to the left in the display. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Page 88
External voltage 5…30 VDC Current 1…10 mA ≈ Residual stress 1 V at 10 mA ≤ 1 µA at 25°C Leak current Electrical isolation 2 kV Max. cable length Resolution see table 11 Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Page 89
Use of Pulse Tester The high-resolution energy and volume pulses can be connected to Kamstrup’s Pulse Tester type 66-99-279 as shown in the below drawing. It is necessary to connect pull-up resistors of e.g. 33 kΩ as shown in the drawing.
Page 90
For calculation of accuracy and precision the registers with RID 223, 155, 229 and 230 – volume, energy, T1 average and T2 average respectively – can be read out after the autointegration. Verification registers Energy EHighRes Volume VHighRes T1 average T1averrage_AutoInt T2 average T2averrage_AutoInt Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
At the very moment PULSE-INOUT1 is connected the verification registers are reset. Maximum 4 seconds after this the verification registers are counted the first time followed by normal counting in the registers every 4 seconds. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Page 92
13.3.3 Pulse resolution in verification mode The resolution of the pulse outputs depends on the actual meter size. In addition to the pulse resolution of ® ® MULTICAL 402 the table includes the resolutions of Kamstrup’s previous compact meters; MULTICAL Compact ® and MULTICAL 401.
EN 1434-1:2007 or OIML R75:2002. The PC-program METERTOOL from Kamstrup includes an energy calculator which is suitable for this purpose: The true energy at the most frequently used verification points is indicated in the table below.
When the installation has been completed, the icon ”METERTOOL HCW” will appear in the ‘All Programs’ menu under ‘Kamstrup METERTOOL’ (or from the menu ”start” for Windows XP) and as a link on the desktop. Double- click on link or icon in order to start the program.
® 14.2 METERTOOL HCW for MULTICAL 14.2.1 Start-up and connection It is important to be familiar with the calculator’s functions before starting programming. The Kamstrup Software product “METERTOOL HCW” (66-99-724) is used for MULTICAL 402. ® ® MULTICAL 402 with USB data cable (66-99-097)
Page 96
In response METERTOOL HCW displays a picture of MULTICAL 402 with information on S/W revision etc. From the menu in the left side of the screen a number of different options are available, depending on mode (Basic/Advanced). Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
It is not possible to change the serial number as it is a unique number allocated to the meter during production. ”Heat/Cooling Change Over” can be disabled depending on the meter type in question. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Page 98
See separate paragraph, 14.3 Verification with METERTOOL HCW. Used for changing between temperature set points during calibration. 14.3.9 Certificate (Advanced Mode) Initiates printing of verification certificates. 14.3.10 Flow Curve Adjustment (Advanced Mode) Please, see section 14.4. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
14.4.3 Update program In this menu the METERTOOL program can be updated if a newer revision is available on Kamstrup’s FTP-server. 14.4.4 Update database In this menu the METERTOOL database can be updated if a newer revision is available on Kamstrup’s FTP-server.
Page 100
Shows the latest activities/functions used in the program. User manual Provides a link to the user manual for the meter on Kamstrup’s website. 14.4.8 About button Lists the METERTOOL program versions and revision numbers as well as all sub-programs, incl. their type numbers and revision numbers, for the entire METERTOOL HCW program.
T2 [°C] 66-99-372 Standard (EN1434/MID) Type 402-W (2-wire Pt500) ∆Θ [K] T1 [°C] T2 [°C] 66-99-373 Standard (EN1434) Type 402-T (2-wire Pt500) For other equipment variants (types or temperature points), please contact Kamstrup A/S. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Page 102
METERTOOL and writing the new data into the equipment. In order to avoid unintentional change of calibration data this writing is protected by a password, which can be obtained from Kamstrup A/S. Calibration data include test points, permissible error, uncertainty, ambient temperature (fixed value) and number of integrations per test.
Page 103
14.5.6 Certificate If you want to print a certificate with saved results, select “Certificate”. The test/verification result can subsequently be found according to serial number, and the certificate can be printed. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Sensor Adjustment” from the menu. This function is password protected and a password can be obtained from ® Kamstrup A/S. Data connection between the PC and MULTICAL 402 can be made either via program cable interface (see below) or verification equipment.
Page 105
Adjustments of more than +/-5% ought not to be made, as they can be due to a flow sensor error. Having been adjusted the flow sensor is now ready for test/verification as well as sealing. Note! Current handling and reverification requirements must be observed. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
402, the read-out includes date and info code of the info event. 14.7.1 Help button Contact The contact button gives you the links to Kamstrup’s website and mailbox. Output This function shows the latest functions used in the program. User manual Links to the user manual for the meter on Kamstrup’s website.
Page 107
To zoom out; doubleclick anywhere on the coordinate system To read exact values on the graphs; deselect Zoom and let the mouse pointer ”hover” over the point of interest. Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
402 has a national German cooling approval based on PTB K7.2. 15.2 The Measuring Instrument Directive ® MULTICAL 402 is available with CE-marking according to MID (2004/22/EC). The certificates have the following numbers: B-module: DK-0200-MI004-013 D-module: DK-0200-MIQA-001 Kamstrup A/S · Technical Description · 5512-742_M1_GB_01.2016...
Repairing the meter, if needed, we recommend only to replace battery, temperature sensors and communication modules. Alternatively, the whole meter should be replaced. Major repairs must be made by Kamstrup A/S. Before sending us the meter to be repaired or checked, please use the error detection table below to help you clarify the possible cause of the problem.
Kamstrup accept outworn MULTICAL for environmentally correct disposal according to previous agreement. The disposal arrangement is free of charge to the customer, except for the cost of transportation to Kamstrup A/S or the nearest disposal system. The meters should be disassembled as described below and the separate parts handed in for approved destruction.