Magnetek 2001-G+M Instruction Manual page 127

Impulse-g+ mini series adjustable frequency crane controls
Hide thumbs Also See for 2001-G+M:
Table of Contents

Advertisement

Parameter
Code
Name
L03.05
Stall Prevention Run
Select
00 Disable
01 Decel Time 1
02 Decel Time 2
Sets a function to prevent stalling during an overload condition while running at constant speed.
Table 5-9:Stall Prevention Run Selection
Setting
00 Disable
01 Decel Time 1
02 Decel Time 2
Function
Enable/Disable stall
prevention during running
See Table 5-9
See Table 5-9
See Table 5-9
Stall prevention/current limit during running is disabled.
Stall prevention/current limit during running is enabled (factory default). When
the inverter output current exceeds the current limit level (L03.06) for more than
100ms during speed agree, the output frequency is decreased according to
deceleration time 1 (B05.02). This can help prevent stalling. When the load
condition is stabilized, the inverter accelerates to the previous frequency.
Stall prevention/current limit running is enabled as in setting "01", however the
output frequency is decreased according to deceleration time 2 (B05.04).
IMPULSE•G+ Mini Advanced Instruction Manual – March 2014
Initial
Range
Value
00–02
01
Description
Access
Level
Basic/Adv
5-67