Air Intake Requirements

The fireplace requires air intake(s) to supply combustion air to the firebox. Requirements for the air
intake(s) are listed below:
The air intake(s) must be routed to the exterior of the structure or to an area that freely conveys
air from the outside. Do not draw air from a garage or other area that may be subject to fumes or
airborne particles.

Air Intake Ducts

Must use 8" UL 181 Duct or better (Class 1 or Class 0 – capable of negative pressure reading of
1" water column). Consult your local building department for details on duct installation and
requirements in your area. We strongly recommend the use of insulated ducting such as Master
Flow™ which is carried at Home Depot™ and other stores that carry HVAC products (insulated
ducting is typically R4.2 or greater with vapor barrier). Insulated ducting prevents condensation
from forming on the exterior of the ducts or fireplace. This is especially important when the ducts
are routed through heated areas that may be subject to humidification.
The chart below details air intake maximum height and length. If the intake falls within the
shaded range, you must contact Travis Industries to verify the installation and determine the
correct configuration.
Connect the air intake ducts to the fireplace, damper (if used), and termination using a suitable
securing method (tape, silicone, etc.). Long duct runs must be properly secured.
We recommend the use of intake dampers. If you do not use dampers, we recommend you route
the intake damper wires to the intake location so dampers may be installed at a later time.
Each air intake termination must be positioned so it does not become blocked by snow,
vegetation, or other material. It must be installed with a suitable cap that prevents water or debris
from entering. The termination (and damper, if used) must be positioned so it may be accessible
for service and verification. If air intake is positioned on a wall, make sure to slope the intake
down slightly to prevent water intrusion.
The air intake termination must be flashed and sealed to meet local building code requirements.
© Travis Industries
Installation
(for qualified installers only)
40 feet (12m)
20 feet (6m)
0 feet
-6 feet (-2m)
9/25/17-1468
Contact Travis
Industries for Details
Standard
Installation
33