Unit Settings and data Reading

4.1 Confirming the I/O Number Allocations and First Word Number

4.1.1 Occupied I/O Area and I/O Allocations

In the FP7, analog input data is allocated to the external input relay area and processed.
An analog input signal into a single channel is handled by 16 X-contact points.
The following table shows the I/O allocation of analog input data.
Input contact
I/O number
CH0
CH1
X0
X20
to
to
XF
X2F
X10
X30
X11
X31
X12
X32
X13
X33
X14
X34
X15
X35
X16
X36
X17
X37
X18
X19
X1A
X1B
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
4-2
CH2
CH3
X40
X60
A/D conversion
to
to
data
(16 bits)
X4F
X6F
Disconnection
X50
X70
detection flag
Upper limit
X51
X71
comparison relay
Lower limit
X52
X72
comparison relay
Upper limit/Lower
X53
X73
limit comparison
execution flag
X54
X74
Not used
Max./Min.
X55
X75
hold execution flag
X56
X76
Not used
X57
X77
Buffer function
execution flag
Buffering flag
Buffering
completion flag
Data before
triggering
enable flag
Name
Digital converted values corresponding to the
analog input is stored.
<Voltage range>
-10 to +10 V: -31,250 to +31,250
0 to +10 V or 0 to +5 V: 0 to +31,250
+1 to +5 V: 0 to +25,000
<Current range>
0 to +20 mA: 0 to +31,250
+4 to +20 mA: 0 to +25,000
* A/D conversion data within the set scale
applies if scale conversion is set.
ON with disconnection detected and OFF
with disconnection restored
(valid for 1 to 5 V and 4 to 20 mA ranges
only)
Turns ON when the value exceeds the set
upper limit.
Turns ON when the value drops below the
set lower limit.
ON when the upper limit/lower limit
comparison function is executed.
Do not use.
ON when the max./min. hold function is
executed.
Do not use.
ON when the buffer function is executed.
ON when buffering starts after the trigger is
accepted.
OFF when the number of buffer data items is
reached.
ON when the shared memory has become
accessible after completion of buffering
OFF on completion of buffer data reading.
ON when the number of buffer data items
before triggering has reached the set value.
OFF on completion of buffer data reading.