Panasonic FP7 User Manual page 69

Analog input unit
Hide thumbs Also See for FP7:
Table of Contents

Advertisement

Individual setting area per channel
Unit
memory
Name
number
(Hex)
UM 00094
UM 000A4
Averaging
constant
UM 000B4
UM 000C4
UM 00095
UM 000A5
Offset value
UM 000B5
UM 000C5
UM 00096
UM 000A6
Gain value
UM 000B6
UM 000C6
UM 00097
Scale
UM 000A7
conversion
UM 000B7
Max. value
UM 000C7
UM 00098
Scale
UM 000A8
conversion
UM 000B8
Min. value
UM 000C8
UM 00099
Upper limit
UM 000A9
comparison
UM 000B9
ON level
UM 000C9
UM 0009A
Upper limit
UM 000AA
comparison
UM 000BA
OFF level
UM 000CA
UM 0009B
Lower limit
UM 000AB
comparison
UM 000BB
OFF level
UM 000CB
UM 0009C
Lower limit
UM 000AC
comparison
UM 000BC
ON level
UM 000CC
(Note) The unit memory numbers in the above table are listed for CH0, CH1, CH2, and CH3 in numerical order.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
8.4 List of Detailed Specifications of Unit Memories
Default
Set constants for average processing.
Function used
Number of
averaging times
K200
Average time
Moving average
Set an offset value at the time of using the offset processing function.
K0
Setting range: -3,000 to +3,000 (specified with a signed integer)
Set an offset value at the time of using the offset processing function.
K10,000
Setting range: +9,000 to +11,000 (0.9x to 1.1x: Specified with a signed
integer)
Set the maximum value at the time of using the scale conversion
function.
K10,000
Setting range: -30,000 to +30,000 (specified with a signed integer)
Set the minimum value at the time of using the scale conversion
function.
K0
Setting range: -30,000 to +30,000 (specified with a signed integer)
Set the upper limit to turn ON the output flag at the time of using the
upper/lower limit comparison function.
K0
Setting range: -31,250 to +31,250 (specified with a signed integer)
Set the upper limit to turn OFF the output flag at the time of using the
upper/lower limit comparison function.
K0
Setting range: -31,250 to +31,250 (specified with a signed integer)
Set the lower limit to turn OFF the output flag at the time of using the
upper/lower limit comparison function.
K0
Setting range: -31,250 to +31,250 (specified with a signed integer)
Set the lower limit to turn ON the output flag at the time of using the
upper/lower limit comparison function.
K0
Setting range: -31,250 to +31,250 (specified with a signed integer)
Setting range and description
Settings
No. of averaging
times
Non-isolated
Isolated
No. of moving
average
2 to 60,000 [times]
1 to 1,500 [ms]
200 to 60,000 [ms]
2 to 2,000 [times]
8-9