CJ
3.19
Thermistor in Remote
Controller Abnormality
Remote Controller Display
CJ
Applicable Models
All indoor models
Method of Error Detection
Error detection is carried out by temperature detected by
room temperature thermistor in remote controller.
Error Decision Conditions
When the room temperature thermistor in remote
controller becomes disconnected or shorted while the
unit is running.
∗ Error code is displayed but the system operates
continuously.
Supposed Causes
Defective room temperature thermistor in remote
controller
Defective remote controller PCB