E3 Abnormal Discharge Pressure - Daikin VRVII Manual

Vrv series pocket manual
Hide thumbs Also See for VRVII:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
E3
3.23
Pressure
Remote Controller Display
E3
Applicable Models
VRV-WII, -WIII, III, III-S and III-Q Series
Method of Error Detection
Abnormality is detected when the contact of the high
pressure protection switch opens.
Error Decision Conditions
Error is generated when the high pressure switch
activation count reaches the number specific to the
operation mode.
Supposed Causes
Actuation of high pressure switch
Defective high pressure switch
Defective outdoor unit main PCB
Instantaneous power failure
Defective high pressure sensor
Abnormal Discharge