For outdoor air thermistor
For suction pipe thermistor
For heat exchanger thermistor
For intermediate heat exchanger thermistor
For liquid thermistor
For remote controller thermistor
T°C
-30
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
370
Troubleshooting by Indication on the Remote Controller
k Ω
361.7719
265.4704
196.9198
147.5687
111.6578
85.2610
65.6705
50.9947
39.9149
31.4796
25.0060
20.0000
16.1008
13.0426
T°C
40
10.6281
45
8.7097
50
7.1764
55
5.9407
60
4.9439
65
4.1352
70
3.4757
75
2.9349
80
2.4894
85
2.1205
90
1.8138
95
1.5575
100
1.3425
105
1.1614
3SA48001 (AD87A001J)