Uc Address Duplication Of Centralized Remote Controller - Daikin VRVII Manual

Vrv series pocket manual
Hide thumbs Also See for VRVII:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
UC
3.68
Centralized Remote Controller
Remote Controller Display
UC
Applicable Models
All indoor models
Centralized remote controller
Method of Error Detection
The principal indoor unit detects the same address as
that of its own on any other indoor unit.
Error Decision Conditions
The error decision is made as soon as the abnormality
aforementioned is detected.
Supposed Causes
Address duplication of centralized remote controller
Defective indoor unit PCB
Troubleshooting
Caution
The centralized address
is duplicated.
Address Duplication of
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
Make setting
change so that
the centralized
address will not
be duplicated.
335

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrvii 4VrviiiVrvii-sVrviii-qVrviii-sVrv-wii

Table of Contents