Ca Thermistor For Discharge Air Abnormality - Daikin VRVII Manual

Vrv series pocket manual
Hide thumbs Also See for VRVII:
Table of Contents

Advertisement

CA
3.17
Air Abnormality
Remote Controller Display
CA
Applicable Models
All indoor models
Method of Error Detection
Error detection is carried out by temperature detected by
discharge air temperature thermistor.
Error Decision Conditions
When the discharge air temperature thermistor becomes
disconnected or shorted while the unit is running.
Supposed Causes
Defective indoor unit thermistor for air outlet
Defective indoor unit PCB
86
Troubleshooting by Indication on the Remote Controller
Thermistor for Discharge