Daikin VRVII Manual page 178

Vrv series pocket manual
Hide thumbs Also See for VRVII:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
Troubleshooting
Caution
Connector is
connected to outdoor
unit PCB.
YES
Resistance
is normal when
measured after
disconnecting the
thermistor from the
outdoor unit
PCB.
CHECK 11
YES
CHECK 11
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
NO
NO
Refer to P.369.
Connect the
connector and
turn ON again.
Replace the
thermistor.
Replace the
outdoor unit
PCB.
173

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrvii 4VrviiiVrvii-sVrviii-qVrviii-sVrv-wii

Table of Contents