5 PIPING AND REFRIGERANT REQUIREMENTS

All fluid and refrigeration connections to the unit, with the exception of the condensate drain, are sweat
copper. Factory-installed piping brackets must not be removed. Field-installed piping must be installed in
accordance with local codes and must be properly assembled, supported, isolated and insulated. Avoid
piping runs through noise-sensitive areas, such as office walls and conference rooms.
Refer to specific text and detailed diagrams in this manual for other unit-specific piping requirements.
All piping below the elevated floor must be located so that it offers the least resistance to air flow. Careful
planning of the piping layout under the raised floor is required to prevent the air flow from being blocked.
When installing piping on the subfloor, we recommend that the pipes be mounted in a horizontal plane
rather than stacked one above the other. Whenever possible, the pipes should be run parallel to the air
flow.
The pipe connection locations, piping general arrangement and schematics are described in the
submittal documents included in the
The following tables list the relevant documents by number and title.
Table 5.1 Piping General-arrangment Drawings
Document Number
Liebert PDX Piping Schematics
DPN002929
DPN003843
DPN002931
DPN002932
DPN002972
Liebert PCW Piping Schematics
DPN002930
DPN003737
Table 5.2 Piping Connection Drawings
Document Number
Downflow Model Primary Connection Locations
DPN002938
DPN002945
DPN002942
DPN002947
DPN003520
DPN003522
DPN002940
DPN002946
Upflow Model Primary Connection Locations
Vertiv | Liebert® PDX™ and PCW™ Installer/User Guide |
Submittal Drawings
on page 106.
Title
Air Cooled Models with TXV
Air Cooled Models with EEV
Water/Glycol Models
GLYCOOL™ Models
Econ-O-Coil Models
Chilled Water Models
Hot Water Reheat
Title
Air Cooled, Raised Floor Models
Air Cooled, Front Discharge Models
Water/Glycol, Raised Floor Models
Water/Glycol, Front Discharge Models
GLYCOOL™ Raised Floor Models
GLYCOOL™ Front Discharge Models
Chilled Water, Raised Floor Models
Chilled Water, Front Discharge Models
29