CANbus & INTERLOCK CONNECTIONS
BETWEEN PDX UNIT & LIEBERT MC CONDENSER (PREMIUM)
COMPONENT NOTES:
1. COMPONENT APPEARANCE, ORIENTATION AND POSITIONINGMAY VARY TERMINAL NAMES AND CALLOUTS REMAIN CONSTANT.
2. ALL CIRCUITS TO THESE CONNECTION POINTS ARE CLASS 2.
CAN & CABLE NOTES (A):
1. CABLE MUSTHAVE THE FOLLOWING SPECIFICATIONS:
- BRAIDED SHIELD OR FOIL SHIELD WITH DRAIN WIRE
- SHIELD MUST BE WIRED TO GROUND AT INDOOR UNIT
- 22-18AWG STRANDED TINNED COPPER
- TWISTED PAIR (MINIMUM 4 TWISTS PER FOOT)
- LOW CAPACITANCE (15pF/FT OR LESS)
- MUST BE RATED TO MEET LOCAL CODES AND CONDITIONS.
- EXAMPLES BELDEN 89207 (PLENUM RATED), OR ALPHA WIRE 6454 CATEGORY 5, 5E, OR HIGHER.
2. DO NOT RUN IN SAME CONDUIT, RACEWAY, OR CHASE AS HIGH VOLTAGE WIRING.
3. FOR CANBUS NETWORK LENGTHS GREATER THAN 450FT(137M), CONTACT FACTORY.
INTERLOCK WIRE NOTES (B):
1. FIELD SUPPLIED WIRE
- 18AWG OR GREATER
- RATED 600V
2. RUN TWO WIRES FROM INDOOR UNIT TO CONDENSER.
DPN003266
Page :2 /2
LIEBERT PDX
REV : 2
REV DATE : 1/17