Liebert PX018 Installer's/User's Manual page 82

Pdx and pcw series thermal management systems, 3 to 8 ton (11 to 29 kw) capacity, upflow and downflow, 60 hz
Table of Contents

Advertisement

Figure 9.13 Steam-generating Humidifier Circuit board diagram
Item
Description
1
PCB is configured for: MES-L
HW Sensor Jumperss
2
Capacity adjust (Default at
3
100%)
4
Sealed, do not adjust
5
Green LED
To configure the correct PCB voltage, set the jumpers as follows:
NOTE: The asterisk (*) indicates a factory setting. Do not adjust.
208V: J6, J9, J15*, J17*, J19*, J10*, J23*, P11 (2-3)*
230V: J5, J9, J15*, J17*, J19*, J10*, J23*, P11 (2-3)*
380V: J3, J8, J15*, J17*, J19*, J10*, J23*, P11 (2-3)*
460V: J2, J8, J15*, J17*, J19*, J10*, J23*, P11 (2-3)*
575V: J1, J8, J15*, J17*, J19*, J10*, J23*, P11 (2-3)*
Vertiv | Liebert® PDX™ and PCW™ Installer/User Guide |
Item
Description
6
Yellow LED
Mains Voltage Select Jumpers
J9: Low Voltage
7
200-240V
J8: High Voltage
380-600V
8
Current transformer
Current Transformer for MES-L 10, loop current-sensing wire twice through current sensing
9
coil.
Current transformer for MES-L 20, loop current-sensing wire once through current-sensing
10
coil.
J6: 200-208
J5: 230V
J3: 380-415
J2: 460V
J1: 575V
82