Liebert PX018 Installer's/User's Manual page 69

Pdx and pcw series thermal management systems, 3 to 8 ton (11 to 29 kw) capacity, upflow and downflow, 60 hz
Table of Contents

Advertisement

Figure 9.2 Remove humidifier high-limit wires
5. Disconnect the actuator from the pipe beneath the right side of the humidifier (if present). See
Figure 9.2 above.
6. Remove the humidifier air block-off panel. See Figure 9.2 above.
7. Locate the humidifier assembly and remove the cover to the electrical compartment.
Disconnect the wires entering the humidifier electric box from the left side. See Figure 9.3
below.
Figure 9.3 Humidifier electric box location
Vertiv | Liebert® PDX™ and PCW™ Installer/User Guide |
Item
Description
1
Humidifier high-limit wires
2
Air-blocking panel
3
Humidifier pan
4
Actuator
Item
Description
1
Humidifier wiring harness
2
Humidifier electric-compartment cover
69