NOTICE
Risk of improper electrical connection of three-phase input power. Can cause backward
compressor rotation and unit damage. Service technicians should use a gauge set on the
system during the initial start up to verify that the three-phase power is connected properly.
The EC fans are not a reliable indicator of proper connection. The blowers will rotate the same
direction, regardless of the three-phase power input. Three-phase power must be connected
to the unit line voltage terminals in the proper sequence so that the compressors rotate in the
proper direction. Incoming power must be properly phased to prevent compressors from
running backward. We recommend checking the unit's phasing with proper instrumentation to
ensure that power connections were made correctly. We also recommend verifying discharge
and suction pressures during start up to ensure that the compressors are running in the
correct direction.
NOTICE
Risk of improper electrical supply connection. Can cause equipment damage.
See transformer label for primary tap connections. Installer will need to change transformer
primary taps if applied unit voltage is other than pre-wired tap voltage.
NOTE: Unit Input Power Requirements: For three-phase units, only three power wires and an earth
ground are required. A neutral is not required at the unit input connections. See
connected Power Supply for PDX and PCW
The electrical connections are described in the submittal documents included in the
on page 106.
The following table lists the relevant documents by number and title.
Table 6.1 Electrical Field-connection Drawings
Document Number
DPN002933
DPN002934
DPN002935
DPN003266
DPN002169

6.1 Wye- and Delta-connected Power Supply for PDX and PCW

Table 6.2 on the facing page shows the acceptable and un-acceptable power supplies by model number
for 208-V to 575-V nominal units. See
on the units.
Vertiv | Liebert® PDX™ and PCW™ Installer/User Guide |
below for detailed information.
Title
Electrical Field Connections, Upflow & Downflow Models
Electrical Field Connections, Downflow Models
Electrical Field Connections, Upflow Models
PDX CANbus & Interlock Connections between PDX Unit & Liebert MC Condenser
Liebert MC Condenser Electrical Field Connections Premium Efficiency Control
Electrical Field
Connections, for the electrical-connection locations
Wye- and Delta-
Submittal Drawings
52

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pw011Px011Px029Px023Pw017Pw029

Table of Contents