3.1 Planning Dimensions

The unit, floor stand, and plenum dimensions are described in the submittal documents included in the
Submittal Drawings
The following table lists the relevant documents by number and title.
Table 3.1 Dimension Planning Drawings
Document Number
Downflow Units
DPN002936
DPN002944
Upflow Units
DPN002937
DPN002971
Floor Stands
DPN002970
DPN002971
Plenums
DPN002981
DPN003697
DPN003447
DPN003610
DPN002936

3.2 Considerations for Air Distribution

Depending on the intake/discharge configuration of the unit, consider the following when preparing for
installation:
When installing a downflow unit with raised-floor discharge:
Verify that the raised floor is properly sized for the unit's airflow and the room is free of airflow
restrictions.
Perforated floor tiles in the raised floor should ensure minimal pressure loss.
The raised floor must provide a minimum of 7-1/2 in. (191 mm) of clearance.
Ensure that there is adequate clearance above the unit for return air. See DPN002936 in the
Submittal Drawings
When installing a downflow units with floor-level discharge:
Provide several feet of clearance for air discharge of the unit.
Ensure that there is adequate clearance above the unit for return air. See DPN002944 in the
Submittal Drawings
When installing upflow units
Provide several feet of clearance for intake and discharge of the unit or for supply and return
ducting.
Provide clearance for service access. See DPN002937 in the
Vertiv | Liebert® PDX™ and PCW™ Installer/User Guide |
on page 106.
Title
Cabinet Dimensional Data, Downflow Models
Cabinet Dimensional Data, Downflow Floor Level Discharge Models
Cabinet Dimensional Data, Upflow Models
Cabinet Dimensional Data, Upflow Rear Return Models
Floorstand & Floor Planning Dimensional Data, Downflow Models
Floorstand Dimensional Data, Upflow Rear Return Models
Plenum Dimensional Data, Upflow Discharge Grille
Plenum Dimensional Data, Upflow Discharge w/ Duct Collar
Plenum Dimensional Data, Top Discharge Upflow Units
Downflow Plenum Dimensional Data
Duct-flange Dimensions, Downflow models, Field-supplied ductwork
on page 106.
on page 106.
Submittal Drawings
on page 106.