Installation Of Outdoor Unit - Gree GWH12ACC-K6DNA1D Service Manual

Hide thumbs Also See for GWH12ACC-K6DNA1D:
Table of Contents

Advertisement

Outdoor
Indoor
Wall pipe
Sealing gum
Fig.16
Note:
Do not bend the drain hose too excessively in order to prevent
blocking.

8.6 Installation of Outdoor Unit

1. Fix the Support of Outdoor Unit(Select it according to
the actual installation situation)
(1) Select installation location according to the house structure.
(2) Fix the support of outdoor unit on the selected location with
expansion screws.
Note:
(1) Take sufficient protective measures when installing the
outdoor unit.
(2) Make sure the support can withstand at least four times the
unit weight.
(3) The outdoor unit should be installed at least 3cm above the
floor in order to install drain joint.(As show in Fig.18)
(4) For the unit with cooling capacity of 2300W~5000W, 6
expansion screws are needed; for the unit with cooling capacity
of 6000W~8000W, 8 expansion screws are needed; for the
unit with cooling capacity of 10000W~16000W, 10 expansion
screws are needed.
Fig.18
At least 3cm above the floor
2. Install Drain Joint(Only for cooling and heating unit)
(1) Connect the outdoor drain joint into the hole on the chassis.
(2) Connect the drain hose into the drain vent.
(As show in Fig.19)
3. Fix Outdoor Unit
(1) Place the outdoor unit on the support.
(2) Fix the foot holes of outdoor unit with bolts.
(As show in Fig.20)
Foot holes
Foot holes
Fig.20
54
Fig.17
Upper hook
Lower hook of
wall-mounting frame
Drain vent
Chassis
Outdoor drain join t
Drain hose
Fig.19
handle
Fig.21
4. Connect Indoor and Outdoor Pipes
(1) Remove the screw on the right handle of outdoor unit and
then remove the handle.(As show in Fig.21)
(2) Remove the screw cap of valve and aim the pipe joint at the
bellmouth of pipe.(As show in Fig.22)
Liquid pipe
Liquid
gas pipe
valve
gas valve
Fig.22
(3) Pretightening the union nut with hand.
(4) Tighten the union nut with torque wrench .
Refer to the following table for wrench moment of force:
Hex nut diameter(mm)
Φ6
Φ9.52
Φ12
Φ16
Φ19
5. Connect Outdoor Electric Wire
(1) Remove the wire clip; connect the power connection wire
and signal control wire (only for cooling and heating unit) to the
wiring terminal according to the color; fix them with screws.(As
show in Fig.23)
blue
Fig.23
blue
Note: the wiring board is for reference only, please refer
to the actual one.
(2) Fix the power connection wire and signal control wire with
wire clip (only for cooling and heating unit).
Note:
(1) After tightening the screw, pull the power cord slightly to
check if it is firm.
(2) Never cut the power connection wire to prolong or shorten
the distance.
6. Neaten the Pipes
(1) The pipes should be placed along the wall, bent reasonably
and hidden possibly. Min. semidiameter of bending the pipe is
10cm.
(2) If the outdoor unit is higher than the wall hole, you must set
a U-shaped curve in the pipe before pipe goes into the room,
in order to prevent rain from getting into the room.(As show in
Fig.24)
Service Manual
Pipe joint
Union nut
Tightening torque(N . m)
15~20
30~40
45~55
60~65
70~75
09/12K
2
3
N(1)
L
N
black
brown
yellow-
blue
brown
yellow-
(black)
green
green
L
N
Indoor unit connection
POWER
N(1)
2
3
L
N
yellow-
green
black brown brown
blue
N
L
POWER
yellow-
green
18/24K
Connect to indoor unit
Installation and Maintenance