3.8 | Wire to door contact
.
Wire the door contact
1
3
2
Figure 3.7: Wiring the door contact
Callout ― Description
1 ― Door Contact
2 ― 1k EOL
3 ― B901 Access Control Module
3.8.1 | Request to Enter (RTE)
Wire the Request to Enter (RTE) device. The strike is activated, and
the door point is shunted when RTE is momentarily shorted to COM.
The Shunt only option shunts the point when this input is momentarily
shorted. To activate the shunt but not the strike, program RTE Shunt
Only? as [YES].
2
1
Figure 3.8: Wiring the RTE
Callout ― Description
1 ― RTE device
2 ― B901 Access Control Module
3.8.2 | Request to Exit (REX)
Wire the Request to Exit (REX) device
.
2
1
Figure 3.9: Wiring the REX
Callout ― Description
1 ― REX device
2 ― B901 Access Control Module
The strike is activated, and the door point is shunted when REX is
momentarily shorted to COM. The Shunt only option shunts the point
when this input is momentarily shorted. To activate the shunt but not
the strike, program REX Shunt Only? as [YES].
NOTICE!
Do not use a Request to Exit device (REX) for emergency
exit applications. NFPA 101 requires that a UL Listed panic
device be used to provide direct power from the standby
power source. Check with your local Authority Having
Jurisdiction (AHJ) prior to installing your system.
4 | Configuration
After you wire the module, power up the system and configure the B901
using Remote Programming Software (RPS) to assign the module to
an assigned area. Whenever possible, be consistent when numbering
doors, areas, and keypads. For example, assign Door 1 to Area 1 and
keypad 1. Test for proper operation.
5 | LED descriptions
The module includes one blue Heartbeat LED, and one Reader
LED. The Heartbeat LED indicates that the module has power as
well as a module's current state. The Reader LED indicates data
transmission. Refer to Table 5.1.
Flash Pattern
Function
Flashes once
Normal state: Indicates normal operation
every 1 sec
state. (blue)
ON Steady
LED trouble state: Module is not powered
(for OFF Steady only), or some other
trouble condition prohibits the module from
OFF Steady
communicating with the control panel.
Flashes rapidly
Card data is executing (yellow)
OFF Steady
No card data is being received
Table 5.1: LED descriptions
6 | Show the firmware version
To show the firmware version using an LED flash pattern:
- If the optional tamper switch is installed:
With the enclosure door open, activate the tamper switch (push and
release the switch).
- If the optional tamper switch is NOT installed: Momentarily short
the T+ terminal.
Refer to Figure 6.1 for an example of flash patterns.
Figure 6.1: Firmware LED flash patterns
When the tamper switch is activated, the heartbeat LED stays OFF
for 3 sec before indicating the firmware version. The LED pulses the
major, minor, and micro digits of the firmware version, with a 1 sec
pause after each digit.
In the following example, the version 1.4.3 shows as LED flashes:
[3 sec pause] *___****___*** [3 sec pause, then normal operation].
NOTICE!
Firmware reprogramming on the B901 is not supported if
connected via the SDI bus. Updating the firmware is achieved
via the SDI2 connection only.
7 | Certifications
Region Certification
USA
UL 294 - Access Control System Units
UL 365 - Police Station Connected Burglar Alarm Units and
Systems
UL 609 - Local Burglar Alarm Units and Systems
UL 864 - Control Units and Accessories for Fire Alarm Systems
UL 985 - Household Fire Warning System Units
UL 1023 - Household Burglar-Alarm System Units
UL 1076 - Proprietary Burglar Alarm Units and Systems
UL 1610 - Central Station Burglar Alarm Units
CSFM - California Office of The State Fire Marshal
FCC Part 15 Class B
CA
Canada CAN/ULC S303 - Local Burglar Alarm Units and Systems
CAN/ULC S304 - Signal Receiving Centre and Premise Alarm
Control Units
ULC-ORD C1023 - Household Burglar Alarm System Units
ULC-ORD C1076 - Proprietary Burglar Alarm Units and Systems
ULC 2016701-S1871E - Fire Alarm and Security Subassemblies
ICES-003 - Information Technology Equipment (ITE)
Approved For
Level Comment
Destructive Attack
I
Line Security
IV
IP or cellular with encryption
Line Security
II
IP or cellular without encryption
Line Security
I
B430/PSTN
Endurance
IV
Send by Power
IV
8 | Specifications
Dimensions
2.9 in x 5.0 in x 0.6 in (73.5 mm x 127 mm x 15.25
mm)
Voltage (input)
12 VDC nominal
Current
Standby: 110 mA + reader current
Alarm: 110 mA + reader current
Alarm output
Form C relay (NC, COM, NO) at 12/24 V @ 2.0 A
Operating
0°C to +50°C (+32°F to +122°F)
temperature
Relative humidity
5% to 93% at +32°C (+90°F) non-condensing
Terminal wire size
18 AWG to 22 AWG (1.02 mm to 0.65 mm)
SDI2/SDI wiring
Maximum distance - wire size (unshielded wire only):
to B901 + Reader
1000 ft (305 m) - 22 AWG (0.65 mm), 2500 ft (762 m)
with external power
- 18 AWG (1.02 mm)
supply
SDI2/SDI wiring to
175 ft (53 m) - 22 AWG (0.65 mm), 450 ft (137 m) -
B901 + Reader from
18 AWG (1.02 mm)
control panel
Wiring distance from
200 ft (61 m) - 22 AWG (0.65 mm), 500 ft (152 m) -
B901 to Reader
18 AWG (1.02 mm) Reader dependant
Bosch compatible
B9512G/B9512G-E/B8512G/B8512G-E/B6512/
control panels
D9412GV4/D7412GV4/D9412GV3/D7412GV3/
D9412GV2/D7412GV2/D9412G/D7412G
(Refer to the control panel installation document for
the number of supported devices.)
Bosch compatible
ARD-AYH12 EM Prox Wall Mount
readers and
ARD-AYJ12 EM Prox Mullion
accessories
ARD-AYK12 EM Prox Mini Mullion
ARD-AYQ12 EM Prox Wall Mount Vandal Resistant
ARD-AYCE65B EM Prox or PIN Mullion
ARD-R10 HID iClass Mini Mullion
ARD-R40 HID iClass Wall Mount
D8223 HID Prox Wall Mount
D8224 HID Prox Mullion
D8224-SP HID Prox Switch Plate Mount
D8225 HID Prox Mini Mullion
D8229 PIN Reader
Bosch compatible
ACA-ATR13 EM Tokens*
credentials
ACD-ATR11ISO EM Cards*
ACD-ATR14CS EM Clamshell Cards
ACD-IC2K26-50 iClass Cards**
ACT-IC2K26-10 iClass Tokens**
D8236-10 HID Prox Cards***
D8236KF-10 HID Prox Tokens***
* EM cards work with EM readers, ** iClass cards work with iClass readers,
*** Prox cards work with Prox readers
Copyright
This document is the intellectual property of Bosch Security Systems, Inc. and
is protected by copyright. All rights reserved.
Trademarks
All hardware and software product names used in this document are likely to be
registered trademarks and must be treated accordingly.
Bosch Security Systems, Inc. product manufacturing dates
Use the serial number located on the product label and refer to the
Bosch Security Systems, Inc. website at
http://www.boschsecurity.com/datecodes/.
Access Control Interface Module