Troubleshooting Guide - Honeywell ADEMCO 4110XM Installation Manual

Hide thumbs Also See for ADEMCO 4110XM:
Table of Contents

Advertisement

Installation and Setup Guide
SYMPTOM
1.
Low Battery message on
keypad.
2.
Periodic beep(s) from keypad.
3.
False alarms.
4.
"AC POWER" light off or
"NO AC" displayed.
5.
Digital communicator mes-
sage not being received.
6.
Does not arm.
7.
Control doesn't respond to
keystrokes on keypad.
8.
"Check 09" is displayed.

Troubleshooting Guide

POSSIBLE CAUSE
1.
System battery is low or missing.
2.
System is in TEST mode.
3a. Sensors not properly installed, wired, or
monitored.
3b. Protected door or window opened while
system armed.
3c. Improper user operation of exit/entry de-
lays.
3d. Magnets located too far from switches,
and/or doors and windows not properly
aligned.
3e. Magnetic contacts improperly connected
or wire broken.
3f.
Entry door programmed as "instant" (e.g.,
Perimeter).
3g. Loose fitting door or window being rattled
by wind or vibrations.
3h. Dust, dirt in sensing chamber of smoke
detector.
3i.
Improper location of smoke detector.
3j.
Unit malfunctioning.
4a. Interrupted AC power supply.
4b. Wire run from transformer to control is too
long.
5a. System in TEST mode.
5b. Telephone connection not secure.
5c. Digital communicator malfunctioning.
5d. Telephone number in program needs
prefix or access code.
5e. Telephone call to central monitoring
station requires operator assistance.
6.
System not ready (zones faulted)..
7a. "CC" displayed.
7b. "dl" displayed.
7c. "OC" displayed.
8.
Keyswitch is enabled but not connected.
1.
Check system battery.
2.
Enter "Code" + OFF to exit TEST mode.
3a. Check installation to see if in accordance
with established procedure.
3b. Check with all occupants of protected
home.
3c. Check setting of entry delay . Exit delay is
15 seconds longer than the entry delay
time. Remind user of same.
3d. Check all openings for proper switch and
magnet orientation.
3e. Check wiring connections. Be sure wires
are properly stripped and tightly fastened
to screw terminals.
3f.
Check and revise programming of zone.
3g. Mount magnet closer to contact.
3h. Clean unit's sensing chamber with vacuum
cleaner per unit's instructions.
3i.
See unit's instructions for locations to
avoid. Relocate as necessary.
3j.
Replace detector.
4a. Check transformer connection and power
line circuit breaker.
4b. Make sure wiring run is not longer than the
recommended length-per-gauge (see
pg.10)
5a. Remove from TEST mode.
5b. Check all connections.
5c. Check with a different 4110.
5d. Program prefix or access code into 4110.
5e. 4110 system cannot work in this situation.
6.
Bypass faulted zones, then arm.
7a. System is in communication with down-
loader at central station. Wait until down-
load session is finished.
7b. System has just been powered and is in its
one minute initialization. To bypass this
time, press '#' + '0'.
7c. No communication between keypad and
control. Check proper keypad
connections.
8.
Connect keyswitch or disable keyswitch.