58
6 6 6 6
Zone 8 Alarm Report Code (Duress)
0 = No Report, 1-9, B-F (as described above).
Console Panic: Key B or *+#
59
6 6 6 6
NOT USED
(must be set to "00")
60
6 6 6 6
Trouble Report Code
0 = No Report, 1-9, B-F (as described above).
Sent if zone has a trouble condition.
61
6 6 6 6
Bypass Report Code
0 = No Report, 1-9, B-F (as described above).
Sent when a zone is manually bypassed.
62
6 6 6 6
AC Loss Report Code
0 = No Report, 1-9, B-F (as described above).
Sent at a random time delay up to 1 hour. If AC is
restored before the report goes out, no report will be
sent.
63
6 6 6 6
Low Battery Report Code
0 = No Report, 1-9, B-F (as described above).
Sent when the system's backup battery has a low-battery
condition.
64
6 6 6 6
Test Report Code
0 = No Report, 1-9, B-F (as described above).
Sent periodically to test that the communicator and
phone lines are operational.
65
6 6 6 6
Open Report Code
0 = No Report, 1-9, B-F (as described above).
Sent upon disarming the system.
66
6 6 6 6
Close Report Code
0 = No Report, 1-9, B-F (as described above).
† 2nd digit is automatically sent as the user number if
expanded or 4+2 reporting is selected.
Sent upon arming the system.
67
6 6 6 6
NOT USED
(must be set to "00")
68
6 6 6 6
Cancel Report Code
0 = No Report, 1-9, B-F (as described above).
Sent upon disarming the system after an alarm has
occurred.
69
6 6 6 6
Group Restores for Trouble and Bypass
0 = No (Report for each restore); 1 = Yes (Report after all
zones restored)
Note: "1" not applicable to Contact ID® Reporting
Restore Report Codes ( 6 6 6 6 69- 6 6 6 6 75)
70
6 6 6 6
Alarm Restore Report Code
0 = No Report, 1-9, B-F (as described above).
2nd Digit is automatically sent as the 2nd digit of the
zone alarm report code programming in *50-*59, if
Expanded or 4+2 reporting is selected.
Sent when an alarm zone is restored to non-faulted
state.
71
6 6 6 6
Trouble Restore Report Code
0 = No Report, 1-9, B-F (as described above).
Sent when a trouble in a zone is restored.
72
6 6 6 6
Bypass Restore Report Code
0 = No Report, 1-9, B-F (as described above).
Sent when a zone that has been bypassed is unbypassed.
73
6 6 6 6
AC Restore Report Code
0 = No Report, 1-9, B-F (as described above).
Sent when AC power has been restored following an AC
power outage.
74
6 6 6 6
Low Battery Restore Report Code
0 = No Report, 1-9, B-F (as described above).
Sent when a system low-battery condition is restored to
normal.
75 -
6 6 6 6 92
NOT USED
6 6 6 6
93
6 6 6 6
Reports per Armed Period
0 = 10 max total alarm + alarm restores; 1 = Unlimited
Limits the number of alarm/alarm restore reports
message pairs per zone sent to the Central Station in an
armed period.
Download Information ( 6 6 6 6 94- 6 6 6 6 97)
94
6 6 6 6
Download Phone No.
Enter up to 12 digits. 0-9 # + 11 for *; # + 12 for #; # +
13 for 2 second pause
Enter the phone number of the downloading computer.
Do not fill unused spaces. If fewer than 12 digits exit
field by pressing * (and press 95, if entering next field).
To clear entries press *94*.
95
6 6 6 6
Ring Detection Count for Downloading
0 = Disable station initiated download; 1-14 = number of
rings (1-9, #+10 for 10, #+11 for 11, #+12 for 12, #+13
for 13, #+14 for 14); 15 = answering machine defeat
96
6 6 6 6
Initialize Download ID and Subscriber
Account Number
This must be done before the first
download. Once initiated, do not re-enter
another subscriber account number
manually. This would void the *96
command.
97
6 6 6 6
Zeroes all Program Fields
Resets all data fields to factory default settings.
Exit Program Mode ( 6 6 6 6 98 or 6 6 6 6 99)
98
6 6 6 6
Exit Programming Mode
Prevents re-entry by [Master Code] + [Code] key + [0]
99
6 6 6 6
Exit Programming Mode
Allows re-entry by [Master Code] + [Code] key + [0]
- 9 -