INSTALLATION OF THE INVERTER
AND INSTRUCTIONS
Installation of the inverter
•
Note - Some inverter models may be installed outside an enclosure. See Appendix 2 for details.
Installation on the enclosure
FR-A720-00900 or less
FR-A740-00440 or less
FR-A760-00330 or less
REMARKS
To use an enclosed brake resistor for the FR-A760-00061 or less, refer to page 8.
General Precaution
•
The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power off, wait for more
than 10 minutes, and check for residual voltage between terminal P/+ and N/- with a meter etc., to avoid a hazard
of electrical shock.
Environment
•
Before installation, check that the environment meets following specifications.
FR-A720/A740
LD, ND (initial setting),HD:
-10°C to + 50°C (14°F to 122°F) (non-freezing)
SLD: -10°C to + 40°C (14°F to 104°F) (non-freezing)
FR-A760
LD, ND (initial setting):
Surrounding air
-10°C to +40°C (14°F to 104°F) (non-freezing) (00840 or less)
temperature
-10°C to +50°C (14°F to 122°F) (non-freezing) (01040 or more)
HD:
-10°C to + 40°C (14°F to 104°F) (non-freezing)
SLD:
-10°C to +30°C (14°F to 86°F) (non-freezing) (00061 or less)
-10°C to +40°C (14°F to 104°F) (non-freezing) (00120 or more)
Ambient humidity
90%RH or less (non-condensing)
Storage temperature
-20°C to +65°C (-4°F to 149°F)
Ambience
Indoors (No corrosive and flammable gases, oil mist, dust and dirt.)
Maximum 1000m (3280.80feet) above sea level for standard operation. After that derate by 3% for
every extra 500m (1640.40feet) up to 2500m (8202feet) (91%).
Altitude, vibration
5.9m/s
2
*1
2.9m/s
or less for the FR-A740-03250 (FR-A760-02210) or more
CAUTION
• Install the inverter on a strong surface securely and vertically with bolts.
• Leave enough clearances and take cooling measures.
• Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity.
• Install the inverter on a non-combustible wall surface.
2
FR-A720-01150 or more
FR-A740-00570 or more
FR-A760-00550 or more
Fix six positions for the FR-A740-03250 to
06830 (FR-A760-02210 to 06630) and fix
eight positions for the FR-A740-07700 to
09620.
2
or less at 10 to 55Hz (directions of X, Y, Z axes)
CAUTION
• When encasing multiple inverters, install them in
parallel as a cooling measure.
• Install the inverter vertically.
10cm(3.94inches)
or more
*2
10cm(3.94inches)
or more
*2
*1 1cm or more for FR-A720-00175
(FR-A740-00090, FR-A760-00061) or less
10cm or more for FR-A720-02880
(FR-A740-01440, FR-A760-01040) or more
*2 20cm or more for FR-A720-02880
(FR-A740-01440, FR-A760-01040) or more
5cm
(1.97inches)
Measurement
position
*1
Vertical
Measurement
position
Inverter
5cm
(1.97inches)
5cm
(1.97inches)