400V class (when input power supply is 440V)
Terminal
Applicable Inverter
Screw
Model
Size
FR-A740-00015 to
M4
00090-NA/N4
FR-A740-00120-NA/
M4
N4
FR-A740-00170-NA/
M4
N4
FR-A740-00230-NA
M5
FR-A740-00310-NA
M5
FR-A740-00380-NA
M6
FR-A740-00440-NA
M6
FR-A740-00570-NA
M6
FR-A740-00710-NA
M8
FR-A740-00860-NA
M8
FR-A740-01100-NA
M8
FR-A740-01440-NA
M10
FR-A740-01800-NA
M10
FR-A740-02160-NA M10(M12)
FR-A740-02600-NA M10(M12)
FR-A740-03250-NA M12(M10)
FR-A740-03610-NA M12(M10)
FR-A740-04320-NA M12(M10)
FR-A740-04810-NA M12(M10)
FR-A740-05470-NA M12(M10)
FR-A740-06100-NA M12(M10)
FR-A740-06830-NA M12(M10)
FR-A740-07700-NA M12(M10)
FR-A740-08660-NA M12(M10)
FR-A740-09620-NA M12(M10)
*1
For the 01100 or less, the cable size is that of the cable (HIV cable (600V class 2 vinyl-insulated cable) etc.) with continuous maximum
permissible temperature of 75°C (167°F). Assumes that the surrounding air temperature is 50°C (122°F) or less and the wiring distance is 20m
(65.62feet) or less.
For the 01440 or more, the recommended cable size is that of the cable (LMFC (heat resistant flexible cross-linked polyethylene insulated cable)
etc.) with continuous maximum permissible temperature of 90°C (194°F). Assumes that the surrounding air temperature is 50°C (122°F) or less
and wiring is performed in an enclosure.
*2
For the 00860 or less, the recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of 75°C
(167°F). Assumes that the surrounding air temperature is 40°C (104°F) or less and the wiring distance is 20m (65.62feet) or less.
For the 01100 or more, the recommended cable size is that of the cable (THHN cable) with continuous maximum permissible temperature of
90°C (194°F). Assumes that the surrounding air temperature is 40°C (104°F) or less and wiring is performed in an enclosure.
(Selection example for use mainly in the United States.)
*3
For the 00860 or less, the recommended cable size is that of the cable (PVC cable) with continuous maximum permissible temperature of 70°C
(158°F). Assumes that the surrounding air temperature is 40°C (104°F) or less and the wiring distance is 20m (65.62feet) or less.
For the 01100 or more, the recommended cable size is that of the cable (XLPE cable) with continuous maximum permissible temperature of 90°C
(194°F). Assumes that the surrounding air temperature is 40°C (104°F) or less and wiring is performed in an enclosure.
(Selection example for use mainly in Europe.)
*4
The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, and a screw for earthing (grounding).
A screw for P/+ terminal for option connection of the 02160 and 02600 is indicated in ( ).
A screw for earthing (grounding) of the 03250 or more is indicated in ( ).
Crimping
Tightening
Terminal
Torque
R/L1,
N·m
*4
U, V, W
S/L2,
T/L3
1.5
2-4
2-4
1.5
2-4
2-4
1.5
5.5-4
5.5-4
2.5
5.5-5
5.5-5
2.5
8-5
8-5
4.4
14-6
8-6
4.4
14-6
14-6
4.4
22-6
22-6
7.8
22-8
22-8
7.8
38-8
38-8
7.8
60-8
60-8
14.7
60-10 60-10
14.7
60-10 60-10
14.7
80-10 80-10
14.7
100-10 100-10
24.5
150-12 150-12
24.5
150-12 150-12
24.5
100-12 100-12 2×100 2×100 2×100
24.5
100-12 100-12 2×100 2×100 2×125
24.5
150-12 150-12 2×125 2×125 2×125
24.5
150-12 150-12 2×150 2×150 2×150
24.5
C2-200 C2-200 2×200 2×200 2×200
24.5
C2-200 C2-200 2×200 2×200 2×200
24.5
C2-250 C2-250 2×250 2×250 2×250
24.5
C2-200 C2-250 3×200 2×250 3×200 2×100 2×500 2×500 2×240 2×240 2×120
2
HIV, etc. (mm
)
*1
R/L1,
Earth
U, V, W P/+, P1
S/L2,
(Ground)
T/L3
Cable
2
2
2
2
2
2
3.5
3.5
3.5
3.5
3.5
3.5
5.5
5.5
5.5
8
8
8
8
8
14
8
14
14
14
14
22
14
22
22
22
14
22
22
22
14
38
38
38
22
60
60
60
22
60
60
60
38
60
60
80
38
80
80
80
38
100
100
100
38
125
150
150
38
150
150
150
38
60
60
60
100
100
100
100
Cable Sizes
AWG/MCM
PVC, etc. (mm
*2
R/L1,
R/L1,
U, V, W
U, V, W
S/L2,
S/L2,
T/L3
T/L3
14
14
2.5
12
14
2.5
12
12
4
10
10
6
8
8
10
6
8
16
6
6
16
4
4
25
4
4
25
1
2
50
1/0
1/0
50
1/0
1/0
50
3/0
3/0
50
3/0
3/0
70
4/0
4/0
95
250
250
120
300
300
150
2×4/0 2×4/0
2×95
2×4/0 2×4/0
2×95
2×250 2×250 2×120 2×120
2×300 2×300 2×150 2×150
2×350 2×350 2×185 2×185
2×400 2×400 2×185 2×185
2×500 2×500 2×240 2×240 2×120
WIRING
2
)
*3
Earth
(Ground)
Cable
2.5
2.5
2.5
4
4
4
6
10
10
10
10
16
16
16
25
16
25
16
50
25
50
25
50
25
50
25
70
35
95
50
120
70
150
95
2×95
95
2×95
95
120
150
2×95
2×95