This section is specifically about safety matters
Do not attempt to install, operate, maintain or inspect the inverter
until you have read through this Installation Guideline and
appended documents carefully and can use the equipment
correctly. Do not use the inverter until you have a full knowledge
of the equipment, safety information and instructions. In this
Installation Guideline, the safety instruction levels are classified
into "WARNING" and "CAUTION".
Incorrect handling may cause hazardous
WARNING
conditions, resulting in death or severe
injury.
Incorrect handling may cause hazardous
CAUTION
conditions, resulting in medium or slight
injury, or may cause only material damage.
The
level may even lead to a serious consequence
CAUTION
according to conditions. Both instruction levels must be followed
because these are important to personal safety.
1. Electric Shock Prevention
WARNING
• While power is ON or when the inverter is running, do not open
the front cover. Otherwise you may get an electric shock.
• Do not run the inverter with the front cover or wiring cover
removed.
Otherwise you may access the exposed high-voltage terminals
or the charging part of the circuitry and get an electric shock.
• Even if power is off, do not remove the front cover except for
wiring or periodic inspection. You may access the charged
inverter circuits and get an electric shock.
• Before wiring, inspection or switching EMC filter ON/OFF
connector, power must be switched OFF. To confirm that, LED
indication of the operation panel must be checked. (It must be
OFF.) Any person who is involved in wiring, inspection or
switching EMC filter ON/OFF connector shall wait for at least 10
minutes after the power supply has been switched OFF and
check that there are no residual voltage using a tester or the like.
The capacitor is charged with high voltage for some time after
power OFF, and it is dangerous.
• This inverter must be earthed (grounded). Earthing (grounding)
must conform to the requirements of national and local safety
regulations and electrical code (NEC section 250, IEC 536 class
1 and other applicable standards).
A neutral-point earthed (grounded) power supply for 400V class
inverter in compliance with EN standard must be used.
• Any person who is involved in wiring or inspection of this
equipment shall be fully competent to do the work.
• The inverter must be installed before wiring. Otherwise you may
get an electric shock or be injured.
• Setting dial and key operations must be performed with dry
hands to prevent an electric shock. Otherwise you may get an
electric shock.
• Do not subject the cables to scratches, excessive stress, heavy
loads or pinching. Otherwise you may get an electric shock.
• Do not replace the cooling fan while power is on. It is dangerous
to replace the cooling fan while power is on.
• Do not touch the printed circuit board with wet hands. You may
get an electric shock.
• When measuring the main circuit capacitor capacity (Pr. 259
Main circuit capacitor life measuring = "1"), the DC voltage is
applied to the motor for 1s at powering off. Never touch the
motor terminal, etc. right after powering off to prevent an electric
shock.
2. Fire Prevention
CAUTION
• Inverter must be installed on a nonflammable wall without holes
(so that nobody touches the inverter heatsink on the rear side,
etc.). Mounting it to or near flammable material can cause a fire.
• If the inverter has become faulty, the inverter power must be
switched OFF. A continuous flow of large current could cause a fire.
• When using a brake resistor, a sequence that will turn OFF
power when a fault signal is output must be configured.
Otherwise the brake resistor may excessively overheat due to
damage of the brake transistor and such, causing a fire.
• Do not connect a resistor directly to the DC terminals P/+ and N/
-. Doing so could cause a fire.
3. Injury Prevention
CAUTION
• The voltage applied to each terminal must be the ones specified in
the Instruction Manual. Otherwise burst, damage, etc. may occur.
• The cables must be connected to the correct terminals. Otherwise
burst, damage, etc. may occur.
• Polarity must be correct. Otherwise burst, damage, etc. may occur.
• While power is ON or for some time after power-OFF, do not touch
the inverter since the inverter will be extremely hot. Doing so can
cause burns.
4. Additional Instructions
Also the following points must be noted to prevent an accidental failure,
injury, electric shock, etc.
(1) Transportation and installation
CAUTION
• The product must be transported in correct method that
corresponds to the weight. Failure to do so may lead to injuries.
• Do not stack the boxes containing inverters higher than the
number recommended.
• The product must be installed to the position where withstands
the weight of the product according to the information in the
Instruction Manual.
• Do not install or operate the inverter if it is damaged or has parts
missing. This can result in breakdowns.
• When carrying the inverter, do not hold it by the front cover or
setting dial; it may fall off or fail.
• Do not stand or rest heavy objects on the product.
• The inverter mounting orientation must be correct.
• Foreign conductive bodies must be prevented to enter the
inverter. That includes screws and metal fragments or other
flammable substance such as oil.
• As the inverter is a precision instrument, do not drop or subject it
to impact.
• The inverter must be used under the following environment:
Otherwise the inverter may be damaged.
LD, ND (initial
Surrounding
setting), HD
*3
air
temperature
SLD
*1
Ambient humidity
Storage temperature
Atmosphere
Altitude, vibration
*1 For the FR-A760-00840 or less, the Surrounding air temperature is -10°C to +40°C
(14°F to 104°F)
*2 For the FR-A760-00061 or less with SLD set, the temperature is -10°C to +30°C
(14°F to 86°F)
*3 For the FR-A760-01040 or more with HD set, the temperature is -10°C to +40°C
(14°F to 104°F)
*4 Temperature applicable for a short time, e.g. in transit.
2
*5 2.9m/s
or less for the FR-A740-03250 (FR-A760-02210) or more.
-10°C to +50°C (14°F to 122°F)
(non-freezing)
-10°C to +40°C (14°F to 104°F)
(non-freezing)
*2
90% RH or less (non-condensing)
-20°C to +65°C
(-4°F to 149°F)
*2
Indoors
(free
from
corrosive
flammable gas, oil mist, dust and dirt)
Maximum 1000m (3280.80feet) above
sea level for standard operation. After
that derate by 3% for every extra 500m
(1640.40feet) up to 2500m (8202feet)
2
(91%). 5.9m/s
or less at 10 to 55Hz
(directions of X, Y, Z axes)
*5
gas,
A-1