Danfoss FC 300 Operating Instructions Manual page 73

Vlt automationdrive 0.25-75 kw
Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

Specifications
1)
High/Normal Load
Typical Shaft output [kW]
Enclosure IP20
Enclosure IP21
Enclosure IP55, IP66
Output current
Continuous (3x380-440 V) [A]
Intermittent (60 s overload)
(3x380-440 V) [A]
Continuous (3x441-500 V) [A]
Intermittent (60 s overload)
(3x441-500 V) [A]
Continuous kVA (400 V AC) [kVA]
Continuous kVA (460 V AC) [kVA]
Max. input current
Continuous (3x380-440 V) [A]
Intermittent (60 s overload)
(3x380-440 V) [A]
Continuous (3x441-500 V) [A]
Intermittent (60 s overload)
(3x441-500 V) [A]
Additional specifications
IP20 max. cable cross-section
5)
(mains and motor)
5)
IP20 max. cable cross-section
(brake and load sharing)
IP21, IP55, IP66 max. cable cross-
section
5)
(mains, motor) [mm
2
2)
(AWG)]
IP21, IP55, IP66 max. cable cross-
5)
section
(brake, load sharing)
2
2)
[mm
(AWG)]
Max cable size with mains
2
2)
disconnect [mm
(AWG)]
Estimated power loss
4)
at rated max. load [W]
Weight,
enclosure IP21, IP55, IP66 [kg]
4)
Efficiency
Table 10.6 Mains Supply 3x380-500 V AC (FC 302), 3x380-480 V AC (FC 301)
For fuse ratings, see 10.3.1 Fuses
1) High overload = 160% torque during 60 s. Normal overload = 110% torque during 60 s.
2) American Wire Gauge.
3) Measured using 5 m screened motor cables at rated load and rated frequency.
4) The typical power loss is at nominal load conditions and expected to be within
cable conditions).
Values are based on a typical motor efficiency (eff2/eff3 border line). Motors with lower efficiency will also add to the power loss in the
frequency converter and opposite.
If the switching frequency is increased compared to the default setting, the power losses may rise significantly.
VLT
®
AutomationDrive Operating
Instructions
P30K
P37K
HO
NO
HO
30
37
37
B4
C3
C1
C1
C1
C1
61
73
73
91.5
80.3
110
52
65
65
78
71.5
97.5
42.3
50.6
50.6
51.8
55
66
66
82.5
72.6
99
47
59
59
70.5
64.9
88.5
35 (2)
50 (1)
35 (2)
50 (1)
50 (1)
50 (1)
50 (1)
50 (1)
50, 35, 35
(1, 2, 2)
570
698
697
45
45
0.98
0.98
®
MG33AM02 - VLT
is a registered Danfoss trademark
P45K
NO
HO
NO
HO
45
45
55
55
C3
C1
C1
90
90
106
106
99
135
117
159
80
80
105
105
88
120
116
158
62.4
62.4
73.4
73.4
63.7
83.7
82
82
96
96
90.2
123
106
144
73
73
95
95
80.3
110
105
143
50 (1)
150 (300 MCM)
50 (1)
50 (1)
150 (300 MCM)
50 (1)
95, 70, 70
(3/0, 2/0, 2/0)
843
891
1083
1022
45
0.98
± 15% (tolerence relates to variety in voltage and
P55K
P75K
NO
HO
NO
75
75
90
C4
C4
C2
C2
C2
C2
147
147
177
162
221
195
130
130
160
143
195
176
102
102
123
104
128
133
133
161
146
200
177
118
118
145
130
177
160
150 (300 MCM)
95 (4/0)
95 (4/0)
150 (300MCM)
95 (3/0)
95 (3/0)
185, 150, 120
(350 MCM, 300
MCM, 4/0)
1384
1232
1474
65
65
0.98
0.99
69
10
10