Checks before replacement
The following shows the check procedure before replacement. In this procedure, stop the control of the online module change
target module for safe online module change.
■Redundant function modules
Check that a redundant function module in the other system is not being changed online.
■I/O modules
1.
Stop all the outputs (Y) and inputs (X).
2.
For an I/O module to which the external power supply is supplied, shut off the external power supply with a switch or
other means.
■I/O modules with diagnostic functions
1.
Stop all the outputs (Y) and inputs (X).
2.
Shut off the external power supply with a switch or other means.
■A/D converter modules (for the R60AD4)
1.
Set A/D conversion disable (1) in 'CH1 A/D conversion enable/disable setting' (Un\G500) of all the channels with an
external device (such as a GOT).
2.
Turn on and off 'Operating condition setting request' (Y9).
3.
Turn off all the Y signals.
4.
Check that the A/D conversion is stopped with 'A/D conversion completed flag' (Un\G42).
To replace other A/D converter modules, also stop the A/D conversion as above. For details on the I/O signals and buffer
memory areas of each A/D converter module, refer to the User's Manual (Application) for the A/D converter module used.
■D/A converter modules (for the R60DA4)
1.
Set D/A conversion disable (1) in 'CH1 D/A conversion enable/disable setting' (Un\G500) of all the channels with an
external device (such as a GOT).
2.
Turn on and off 'Operating condition setting request' (Y9).
3.
Turn off all the Y signals.
4.
Shut off the external power supply with a switch or other means.
5.
Check that the D/A conversion is stopped and the analog output value is 0V/0mA.
To replace other D/A converter modules, also stop the D/A conversion as above. For details on the I/O signals and buffer
memory areas of each D/A converter module, refer to the User's Manual (Application) for the D/A converter module used.
■Temperature input modules (for the R60TD8-G)
1.
Set Conversion disable (1) in 'CH1 Conversion enable/disable setting' (Un\G500) of all the channels with an external
device (such as a GOT).
2.
Turn on and off 'Operating condition setting request' (Y9).
3.
Turn off all the Y signals.
4.
Check that the temperature conversion is stopped with 'Conversion completed flag' (Un\G42).
To replace other temperature input modules, also stop the temperature conversion as above. For details on the I/O signals
and buffer memory areas of each temperature input module, refer to the User's Manual (Application) for the temperature input
module used.
3 REPLACEMENT PROCEDURE
30
3.4 Changing a Module by Controlling Special Relays and Special Registers