Plastic (Pps) Balanced Flue System For External Wall Connection; Cen/Tr 1749); Max. Total Length Of The Flue Pipe - Viessmann Vitodens 100-W Technical Manual

Flue systems for gas condensing boilers vitodens series; vitosolar series up to 150.0 kw
Hide thumbs Also See for Vitodens 100-W:
Table of Contents

Advertisement

Design and sizing information for connection on the flue gas side
Vitodens 300-W, 333-F, 343-F and Vitosolar 300-F with Vitodens 300-W
Rated heating output range
a
Max. length – system size 60/100
a
Max. length – system size
*1*2
80/125
b
Min.
2 x 87° balanced flue bends are taken into consideration for the
maximum flue lengths.
2.5 Plastic (PPs) balanced flue system for external wall connection (type C
1749)
As part of the CE approval test it was verified that surface tempera-
tures on the Vitodens and its balanced flue system do not exceed
85 °C at any point.
Observe the design information to CEN/TR 1749, in particular
the arrangement/position of the wall terminal.
Install the connection line with a fall of at least 3° to the boiler.
Install an inspection port in the flue for checking and cleaning the
flue pipe.
The flue for external wall connection has been certified as a concen-
tric balanced flue system with the Vitodens condensing boiler.
A performance verification to EN 13384 is not required.
a
1
4
6 3
5
32
C
A Ventilation air
B Flue gas
C Inspection port

Max. total length of the flue pipe

Vitodens 100-W and 111-W
Rated heating output range
Max. length – system size 60/100
Max. length – system size 80/125
Vitodens 200-W, 222-F, 222-W and 242-F
Rated heating output range
a
Max. length – system size 60/100
a
Max. length – system size 80/125
*1
Alternative system size. Balanced flue adaptor must be ordered separately.
*2
Alternative system size. Balanced flue adaptor must be ordered separately.
VITODENS, VITOSOLAR
kW
m
m
mm
A
7
B
kW
m
m
*1*2
kW
m
*1*2
m
11
19
10
10
13
13
400
400
If fitting other bends, tees or straight lengths, subtract the following
values from the maximum length:
■ Balanced flue bends 45°: 0.5 m
■ Balanced flue bends 87°: 1 m
■ Balanced flue inspection tee: 1.5 m
1 Boiler flue connection (part of the
standard boiler delivery)
2 Balanced flue external wall con-
nection (incl. wall bezels)
3 Balanced flue pipe
1 m long
0.5 m long
4 Balanced flue bend
87° (1 pce)
45° (2 pce)
or
Balanced flue inspection bend 87°
(1 pce)
5 Balanced flue inspection piece,
straight (1 pce)
6 Balanced flue slide coupling
7 Grille
Required if the combustion air inlet
and flue outlet are positioned up to
2 m above ground level in public or
private thoroughfares
Fixing clamp, white (1 pce)
Balanced flue adaptor
– Ø 80/125 mm to Ø 60/100 mm
– Ø 60/100 mm to Ø 80/125 mm
19
26
10
10
13
13
19
10
13
(cont.)
26
10
13
400
400
to CEN/TR
13x
System size Ø mm
60
80
110
60
80
110
60
80
110
60
80
110
60
80
60
80
110
60
80
110
60
80
110
60
80
110
60
80
60
80
30
8
11
26
30
10
8
13
11
VIESMANN
35
10
11
2
35
8
11
35
8
11
21