Design and sizing information for connection on the flue gas side
Vitodens 200-W, from 49 kW
Rated heating output range
Max. length – system size 80
Max. length – system size 110
Vitodens 300-W, 333-F, 343-F and Vitosolar 300-F with Vitodens 300-W
Rated heating output range
Max. length – system size 60
Max. length – system size 80
The following components are taken into consideration for the maxi-
mum flue lengths:
2
■ Connection pipe D 1 m long.
■ 1 bend 87° and 1 support bend 87°
or
■ 2 bends 45° and 1 support bend 87°
If fitting other bends, tees or straight lengths, subtract the following
values from the maximum length:
■ Connection pipe 0.5 m long: 0.5 m
■ Connection pipe 1 m long: 1 m
*1
Alternative system size. Balanced flue adaptor must be ordered separately.
*2
Alternative system size. Balanced flue adaptor must be ordered separately.
VIESMANN
38
kW
m
m
kW
m
*1*2
m
49
60
20
15
*1*2
*1*2
25
20
11
15
17
■ 45° bend: 0.3 m
■ 87° bend: 0.5 m
■ Inspection tee: 0.3 m
Note
Observe the specifications regarding internal shaft dimensions (see
page 36).
(cont.)
80
99
120
20
20
20
19
26
15
15
17
20
VITODENS, VITOSOLAR
150
20
35
11
15