Plastic (Pps) Balanced Flue System For External Wall Connection; 13X To Trgi 2008); Max. Total Length Of The Flue Pipe - Viessmann VITODENS Technical Manual

Flue systems for gas condensing boilers
Hide thumbs Also See for VITODENS:
Table of Contents

Advertisement

Design and sizing information for connection on the flue gas side
Subtract additional bends, tees and straight lengths from the maximum
length using the following values:
■ Balanced flue bends 45°: 0.5 m
■ Balanced flue bends 87°: 1 m
■ Balanced flue inspection tee: 1.5 m
2.4 Plastic (PPs) balanced flue system for external wall connection (type C
As part of the CE approval test it was verified that no surface temper-
atures on the Vitodens or its balanced flue system will exceed 85 °C.
Observe the implementation information to TRGI 2008, in partic-
2
ular the arrangement/position of the wall terminal.
Install the connecting pipe with a minimum fall of 3° towards the
boiler.
1
4
6 3
5
C
A Ventilation air
B Flue gas
C Inspection port

Max. total length of the flue pipe

Vitodens 200-W, 222-F, 222-W and 242-F
Rated heating output range
a
Max. length - system size 60
a
Max. length - system size 80
a
Max. length - system size 100
Vitodens 300-W, 333-F and 343-F
Rated heating output range
a
Max. length - system size 60
a
Max. length - system size 80
2 x 87° balanced flue bends are taken into consideration for the max-
imum flue lengths.
Alternative system size. Balanced flue adaptor must be ordered separately.
*1
VIESMANN
20
a
32
A
kW
m
m
m
Install an inspection port in the flue for checking and cleaning the flue
pipe.
The external wall connection has been tested and CE-designated as
a concentric balanced flue system as one structural unit with the
Vitodens condensing boiler.
A performance verification according to EN 13384 is not required.
1
Boiler flue connection (part of the stand-
ard boiler delivery)
2
Balanced flue external wall connection
(incl. wall bezels)
7
3
Balanced flue pipe
B
1 m long
0.5 m long
4
Balanced flue bend
87° (1 pce)
45 ° (2 pce)
or
Balanced flue inspection bend, 87° (1
pce)
5
Balanced flue inspection piece, straight
(1 pce)
6
Balanced flue slide coupling
7
Grille
Required if the combustion air inlet and flue
outlet are positioned up to 2 m above
ground level in public or private thorough-
fares
Fixing clamp, white (1 pce)
Balanced flue adaptor
– Ø 80/125 mm to Ø 60/100 mm
– Ø 60/100 mm to Ø 80/125 mm
3.2–13
3.2–19
5.2–26
10
10
10
*1
*1
*1
13
13
13
kW
1.9–11
m
10
m
*1
13
Subtract additional bends, tees and straight lengths from the maximum
length using the following values:
■ Balanced flue bends 45°: 0.5 m
■ Balanced flue bends 87°: 1 m
■ Balanced flue inspection tee: 1.5 m
(cont.)
to TRGI 2008)
13x
System size Ø
mm
60
60
60
60
60
60
60
60
60
60
60
5.2–35
17–45
17–60
30–80
8
*1
10
10
11
*1
*1
13
13
1.9–19
4.0–26
10
10
*1
*1
13
13
VITODENS AND VITOSOLAR
80
80
80
80
80
80
80
80
80
80
80
30–100
13
13
4.0–35
8
*1
11