Connecting The Single Phase Inverter - SolarEdge SE3000US Installation Manual

Single phase inverter
Table of Contents

Advertisement

NOTE
Inverters that are maked in the diagram above with two asterisks (**) and that have
their Neutral line connected can be set with the Auto Detect Grid option. In this
case, there is no requirement to configure them to a specific grid voltage.
Inverters that are connected to corner grounded grids must have the L2 terminal
connected to the grounded conductor. For all other grids, L1 and L2 are
interchangable.
NOTE
When connecting multiple single phase inverters in an installation connected to a
three-phase grid, phase balancing may be required by the utility or grid operator.
Phase balancing is supported in the SolarEdge inverters. Please refer to the
SolarEdge Phase Balancing Manual for more details.

Connecting the Single Phase Inverter

Connectors and Cables
The following shows the Single Phase Inverter connectors:
Figure 12: Single Phase Inverter Connectors
SolarEdge Installation Guide – MAN-01-00002-1.6
Installing the Inverter
DC Input
RS232
ON/OFF Switch
LCD Button
AC Output
Communication
Glands