Refer to the following table to determine the correct fuse size to use at the
connection point of the Single Phase Inverter to the grid:

Inverter

SE3000
SE3800
SE5000
SE6000
SE7000
SE3000
SE3800
SE5000
SE6000
SE7000
SE3000
SE3800
SE5000
SE6000
SE7000
WARNING!
For more wiring information, you may refer to the Application Note called
SolarEdge Recommended AC Wiring, which can be accessed from the SolarEdge
website.
Pour plus d'informations de câblage, vous pouvez vous référer à la Note
d'application appelée
consultée sur le site SolarEdge.
SolarEdge Installation Guide – MAN-01-00002-1.6
Maximum Output Current
208 VAC
14.5 A
18.5 A
24 A
25 A
25 A
240 VAC
12.5 A
16 A
21 A
25 A
25 A
277 VAC
---
---
18.5 A
22 A
25 A
SolarEdge Recommended AC Wiring,
Installing the Inverter
Suggested Breaker
or Fuse
20 A
25 A
30 A
35 A or 40 A
35 A or 40 A
20 A
20 A
30 A
35 A or 40 A
35 A or 40 A
---
---
25 A
30 A
35 A or 40 A
qui peut être