Chapter 3: Installing The Inverter; Identifying The Inverter; Selecting The Mounting Location; Chassis Clearance - SolarEdge SE3000US Installation Manual

Single phase inverter
Table of Contents

Advertisement

Chapter 3
Installing the Inverter
The Single Phase Inverter can be installed either before or after the PV modules
and power optimizers have been installed.

Identifying the Inverter

Refer to the stickers on the side of the inverter that specify its Serial # and its
Electrical Ratings including its Max Output Power. Please provide the serial
number when contacting the SolarEdge support line. The serial number is also
required when requesting to open a new site in the SolarEdge Monitoring Portal.

Selecting the Mounting Location

This process involves attaching the inverter mounting bracket to a wall or pole
and then mounting the Single Phase Inverter onto it.

Chassis Clearance

The heat dissipation solution requires the following clearance areas between the
Single Phase Inverter chassis and all types of obstructions, such as wires and
walls:
8" (20 cm) to the top and bottom of the chassis
4" (10 cm) to the right and left of the chassis
NOTE:
If more than one Single Phase Inverter is installed side by side, the distances
between them must exceed 4" (10 cm).
SolarEdge Installation Guide – MAN-01-00002-1.6
Installing the Inverter
27

Hide quick links: