Mitsubishi Electric Netcom 2 User Manual page 41

Table of Contents

Advertisement

Mitsubishi Netcom User Manual
DESCRIPTION
"The output line identifier."
::= { upsOutputEntry 1 }
upsOutputVoltage OBJECT-TYPE
SYNTAX
NonNegativeInteger
ACCESS
read-only
STATUS
mandatory
DESCRIPTION
"The present output voltage (0.1 RMS Volt)."
::= { upsOutputEntry 2 }
upsOutputCurrent OBJECT-TYPE
SYNTAX
NonNegativeInteger
ACCESS
read-only
STATUS
mandatory
DESCRIPTION
"The present output current (0.1 RMS Amp)."
::= { upsOutputEntry 3 }
upsOutputPower OBJECT-TYPE
SYNTAX
NonNegativeInteger
ACCESS
read-only
STATUS
mandatory
DESCRIPTION
"The present output true power (watts)."
::= { upsOutputEntry 4 }
upsOutputPercentLoad OBJECT-TYPE
SYNTAX
INTEGER
ACCESS
read-only
STATUS
mandatory
DESCRIPTION
"The percentage of the UPS power capacity presently being
used on this output line (the greater of the percent load
of true power capacity and the percent load of VA."
::= { upsOutputEntry 5 }
upsBypass OBJECT IDENTIFIER ::= { MitsubishiUPS 5 }
upsBypassFrequency OBJECT-TYPE
SYNTAX
NonNegativeInteger
ACCESS
read-only
STATUS
mandatory
DESCRIPTION
"The present bypass frequency."
::= { upsBypass 1 }
upsBypassNumLines OBJECT-TYPE
SYNTAX
NonNegativeInteger
ACCESS
read-only
STATUS
mandatory
DESCRIPTION
"The number of bypass lines utilized in this device.
entry indicates the number of rows in the bypass table."
::= { upsBypass 2 }
Rev 3 02/24/2009
-- UNITS 0.1 RMS Volts
-- UNITS 0.1 RMS Amp
-- UNITS Watts
-- UNITS percent
-- UNITS 0.1 Hertz