STATUS mandatory
DESCRIPTION
"The UPS is drawing power from the batteries."
::= { upsWellKnownAlarms 2 }
upsAlarmLowBattery OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The remaining battery run-time is less than or equal
to upsConfigLowBattTime."
::= { upsWellKnownAlarms 3 }
upsAlarmDepletedBattery OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The UPS will be unable to sustain the present load
when and if the utility power is lost."
::= { upsWellKnownAlarms 4 }
upsAlarmTempBad OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"A temperature is out of tolerance."
::= { upsWellKnownAlarms 5 }
upsAlarmInputBad OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"An input condition is out of tolerance."
::= { upsWellKnownAlarms
upsAlarmOutputBad OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"An output condition (other than OutputOverload) is
out of tolerance."
::= { upsWellKnownAlarms
upsAlarmOutputOverload OBJECT-TYPE
SYNTAX INTEGER
ACCESS read-only
STATUS mandatory
DESCRIPTION
"The output load exceeds the UPS output capacity."
::= { upsWellKnownAlarms 8 }
upsAlarmOnBypass OBJECT-TYPE
Rev 3 02/24/2009
6 }
7 }