Modbus RTU RS-485
APPENDIX C
05 (0x05) Force single coil
Query
Slave address
Function
Coil Address Hi
Coil Address Lo
Force Data Hi
Force Data Lo
CRC
Examples
Coil 0 (Restart Modbus communication)
To activate a new baudrate and parity/framing the coil 0 (restart Modbus communication)
must be send. Otherwise a power down/up initiate a new baudrate and parity/framing:
Query:
1,5,0,0,255,0,140,58 (Set coil 0 to 0xFF00)
Receive:
1,5,0,0,255,0,140,58 (Restart Modbus communication)
16 (0x10) Write multiple registers
Query
Slave address
Function
Starting Address Hi
Starting Address Lo
No. of Registers Hi
No. of Registers Lo
Byte Count
Data Hi
Data Lo
:
Data Hi
Data Lo
CRC
Examples
Set baud rate to 115200 baud
Query:
1,16,2,17,0,1,2,0,8,135,23 (115200 = value 8)
Receive:
1,16,2,17,0,1,80,116
To activate a new baudrate and parity/framing the coil 0 (Restart Modbus communication)
must be send.
Otherwise a power down/up initiate a new baudrate and parity/framing:
Query:
1,5,0,0,255,0,140,58 (Set coil 0 to 0xFF00)
Receive:
1,5,0,0,255,0,140,58 (Restart Modbus communication)
SFIDK.PS.023.D2.02
Response
1 byte
Slave address
1 byte
Function
1 byte
Coil Address Hi
1 byte
Coil Address Lo
1 byte
Force Data Hi
1 byte
Force Data Lo
2 bytes
CRC
Response
1 byte
Slave address
1 byte
Function
Starting Address Hi
1 byte
1 byte
Starting Address Lo
1 byte
No. of Registers Hi
1 byte
No. of Registers Lo
1 byte
CRC
1 byte
1 byte
1 byte
1 byte
2 bytes
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
2 bytes
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
2 bytes
29