Modbus RTU RS-485
7.

Modbus coils

7.1 Communication
settings

7.2 Auto zero adjust

7.3 Totalizer

7.4 Batch

26
7.
Modbus coils
In the following the coils for the USM II Modbus RTU module are described.
Figure:
Memory map for coils
Modbus
Modbus
register
address
0:00001
0
Modbus
Modbus
register
address
0:00009
8
Modbus
Modbus
register
address
0:00010
9
0:00011
10
0:00012
11
0:00013
12
Modbus
Modbus
register
address
0:00014
13
0:00015
14
SFIDK.PS.023.D2.02
Control/status
Data
Description
type
Restart Modbus communication:
Coil
Write:
0 = No effect
1 = Restart
Read:
always 0
Data
Description
type
Coil
Start auto zero adjust:
Write:
0 = No effect
1 = StartRead:
0 = Idle1 = Busy
Data
Description
type
Coil
Reset totalizer 1:
Write:
0 = No effect
1 = ResetRead:
always 0
Coil
Hold totalizer 1:
Write:
0 = Run
1 = HoldRead:
0 = Not held1 = Held
Coil
Reset totalizer 2:
Write:
0 = No effect
1 = ResetRead:
always 0
Coil
Hold totalizer 2:
Write:
0 = Run
1 = HoldRead:
0 = Not held1 = Held
Data
Description
type
Coil
Start Batch:
Write:
0 = Stop Batch
1 = Start BatchRead:
0 = Stopped1 = Not stopped
Coil
Pause Batch:
Write:
0 = Resume Batch
1 = Pause BatchRead:
0 = Not paused1 = Paused
0
20
655535
Read/
write
R/W
Read/
write
R/W
Read/
write
R/W
R/W
R/W
R/W
Read/
write
R/W
R/W