Modbus RTU RS-485

6.12 Flowmeter status

6.
Modbus holding registers
Modbus
Modbus
register
address
4:03201
3200
4:03202
3201
4:03203
3202
4:03204
3203
4:03205
3204
4:03206
3205
4:03207
3206
4:03208
3207
4:03209
3208
4:03210
3209
4:03211
3210
* Further information about the Error pending numbers can be found in the MAG/MASS 6000 manuals.
Zero adjust progress MAG
Modbus
Modbus
register
address
4:03212
3211
Zero adjust progress MASS
Modbus
Modbus
register
address
4:03212
3211
SFIDK.PS.023.D2.02
No. of
Data
Description
bytes
type
2
Word
System status:
bit0=RunIndicator
bit1=ErrorPendingOn
bit2=ErrPendChanged
bit3=Batching
bit4=BatchPaused
bit5=Zeroadjusting
bit6=Totalizer1Hold
bit7=Totalizer2Hold
2
Word
Error pending 1* (oldest/first error)
0xFFFF = no error
2
Word
Error pending 2*
2
Word
Error pending 3*
2
Word
Error pending 4*
2
Word
Error pending 5*
2
Word
Error pending 6*
2
Word
Error pending 7*
2
Word
Error pending 8*
2
Word
Error pending 9*
2
Byte
Batch status
0 = Idle
1 = Ready
2 = Running
3 = Paused
No. of
Data
Description
bytes
type
Zero adjust progress
2
Byte
0 = Idle
1 = Ready
2 = Running
No. of
Data
Description
bytes
type
4
Float
Zero adjust progress (0-100 %)
Read/
write
R
R
R
R
R
R
R
R
R
R
R
Read/
write
R
Read/
write
R
25