4.8

RS485 interface - X12

The SINAMICS V90 servo drives support communication with the PLCs through the RS485 interface over the USS or
Modbus protocol.
Pin assignment
Illustration
Type: 9-pin, Sub-D, female
62
Pin
Signal name
1
Reserved
2
Reserved
3
RS485+
4
Reserved
5
6
3.3 V
7
Reserved
8
RS485-
9
Reserved
Do not use
Do not use
RS485 differential signal
Do not use
M
Ground to internal 3.3 V
3.3 V power supply for internal signal
Do not use
RS485 differential signal
Do not use