Ablerex 625L Manual page 2

Advertisement

2. Check Battery LED (
):
˙
Red LED flashes every 0.5 seconds and buzzer alarms every 0.5 seconds when UPS is in battery
low condition.
3. Main Switch:
˙
To Control on/off the UPS when Utility is normal.
˙
To enable "DC-Start" Function when Utility fails. ( To enable DC Start properly, you are
recommended to connect <80% output load with the UPS only)
.......................................................................................................................
ABLEREX 1000L / 1500L
1. Line LED (
):
˙
Green LED remains standstill when Utility is normal.
˙
Green LED flashes every 2 seconds when the UPS is in Battery
charging mode.
˙
Green LED remains standstill and simultaneously buzzer alarms
continuously when the UPS is in overload condition.
2. Inverter LED (
):
˙
Yellow LED flashes every 2 seconds and simultaneously buzzer alarms continuously when Utility
failure.
3. Overload LED (
)
˙
Red LED remains standstill and simultaneously buzzer alarms continuously when the UPS is in
overload condition.
4. Check Battery LED (
)
˙
Red LED flashes every 0.5 seconds and buzzer alarms every 0.5 seconds when UPS is in battery
low condition.
5. Main Switch:
˙
To Control on/off the UPS when Utility is normal.
˙
To enable "DC-Start" Function when Utility fails. (To enable DC Start properly, you are
recommended to connect <80% output load with the UPS only)
NOTE: Make sure the computer connected to the UPS is switched on before enable the "DC-Start"
function. You are not recommended to add some other computer or peripherals after DC-Start function
is activated.
REAR PANEL EXPLANATION
1. AC Inlet
ABLEREX 625L
2. Backup Outlets:3pcs NEMA5-15R or IEC320
3. USB Interface.
4. RJ11/RJ45 Jacks:MODEM /LAN Protection
5. Site Wiring Fault Indicator:For 115Vac system only.
6. AC Fuse Holder. (W/fuse):625VA/115Vac/8A and
625VA/230Vac/6.5A
.....................................................................
1. AC Inlet
ABLEREX 1000L / 1500L
2. Backup Outlets:6pcs NEMA5-15R, Local socket or IEC320
3. Computer Interface:True RS232 communication port.
4. RJ11/RJ45 Jacks: MODEM /LAN Protection
5. Site Wiring Fault Indicator: For 115Vac system only.
6. USB Interface.
7. Fuse.
1 2
5
3 4
USB
IN
OUT
U SB
IN
OUT
USB
IN
OUT
AC INP UT
AC INP UT
AC IN P UT
REPLACING THE BATTERY
NOTE:Once the battery is disconnected, the loads are not protected from power outages.
ABLEREX 625L
Use a cross-type screwdriver to remove the two
front panel screws and slide down the panel.
ABLEREX 1000L / 1500L
Use a cross-type screwdriver to remove the two
top cover screws and slide back the cover. Please
refer to the figures STEP 1 through STEP 4.
1. Gently Pull the battery out of the UPS.
2. Loosen the black wire from the negative (-) terminal
and red wire from the positive (+) terminal.
3. Connect the battery leads to the new battery.
Note:Small sparks at the battery connectors are normal during connection.
4. Slide the battery into the UPS.
5. Close the front panel and fasten two screws.
6. Dispose of the old battery properly at an appropriate recycling facility.
TROUBLE SHOOTING
Situation
Check Items
Mains normal but 'Line' LED
1. Is the power switch on?
is not on.
2. Is the fuse in order?
3. Is the power cord loose?
'Line' LED flashes every
Battery voltage is too low
second but no output
Alarm buzzer beeps
Check to see load status if it is
continuously when Utility is
in overload.
normal.
Alarm buzzer beeps for 10
seconds, then the UPS is
turned off
No LEDs display on the front
panel
UPS dose not provide
1. The UPS's battery is weak
expected back up time.
due to recent outage.
2. The UPS's battery is near
the end of its service life.
The UPS operates normally,
Building wiring error such as
but the site wiring fault
missing ground or hot to
indicator is lit.
neutral wire reversal.
Automatic Shutdown Software can be downloaded at www.ablerex.com.sg
192321942013000
-
Solution
1. Press Main Switch on.
2. Change fuse w/same rating.
3. Re-connect the power cord
properly.
Recharge the UPS for 24
hours.
Remove some uncritical load.
Remove some uncritical load
and re-switch on the UPS.
Consult with your sales agent
for help.
1. Charge the battery.
2. If the battery is near the end
of its service lift, consider
replacing the battery.
Have a qualified electrician
correct the building wiring.