DVC5000 Digital Valve Controller
May 2018
Either of these choices (Dynamic Variable or Device Variable ID) can be substituted for the "#" sign in the Variable
Identifier fields below.
Variable Identifier
Comments / Explanation
#
See any of the variable identifiers in the table immediately above.
#_CLASS
Always "0".
#_CODE
The "Device Variable ID" number in the table immediately above.
#_HEALTHY
A "true" or "false" indication of the health of the sensor providing this value.
#_STATUS
#_UNITS
Decimal "Variable Units code" number from the "Units Codes" table on page 6.
Device Status:
The eight standard status conditions (present in ANY HART field device) are all represented by a Boolean "true" or
"false" state. These eight conditions, discussed on page 7, are:
D DEVICE_MALFUNCTION
D CONFIGURATION_CHANGED
D COLD_START
D MORE_STATUS_AVAILABLE
D LOOP_CURRENT_FIXED
D LOOP_CURRENT_SATURATED
D NONPRIMARY_VALUE_OUT_OF_LIMITS
D PRIMARY_VALUE_OUT_OF_LIMITS
26
Instruction Manual Supplement
D103266X012