Emerson Fisher FIELDVUE DVC5000 Instruction Manual Supplement page 26

Digital valve controllers
Table of Contents

Advertisement

DVC5000 Digital Valve Controller
May 2018
Either of these choices (Dynamic Variable or Device Variable ID) can be substituted for the "#" sign in the Variable
Identifier fields below.
Variable Identifier
Comments / Explanation
#
See any of the variable identifiers in the table immediately above.
#_CLASS
Always "0".
#_CODE
The "Device Variable ID" number in the table immediately above.
#_HEALTHY
A "true" or "false" indication of the health of the sensor providing this value.
#_STATUS
#_UNITS
Decimal "Variable Units code" number from the "Units Codes" table on page 6.
Device Status:
The eight standard status conditions (present in ANY HART field device) are all represented by a Boolean "true" or
"false" state. These eight conditions, discussed on page 7, are:
D DEVICE_MALFUNCTION
D CONFIGURATION_CHANGED
D COLD_START
D MORE_STATUS_AVAILABLE
D LOOP_CURRENT_FIXED
D LOOP_CURRENT_SATURATED
D NONPRIMARY_VALUE_OUT_OF_LIMITS
D PRIMARY_VALUE_OUT_OF_LIMITS
26
Instruction Manual Supplement
D103266X012