Annex B DVC5000 Parameters as part of a Rosemount 1410 /
1420 WirelessHART Gateway
A FIELDVUE DVC5000 can join a wireless network through the addition of a Rosemount 775 THUM WirelessHART
adapter. The wireless adapter acts both as a HART modem for communications coming to the DVC5000 from
application software and as an independent master issuing commands periodically to the wired device pertaining to
the device's status. This independently gathered status information is relayed back to the Rosemount 1410 or 1420
Wireless Gateway and is made available to the user either through viewing the HTML interface or via mapping as
"Published Data" parameters via the Gateway's MODBUS or OPC outputs.
For HART 5 devices the PV, SV, TV, and QV variables can be mapped.
Configure the THUM as follows:
Navigate to Configure > Manual Setup
Under the Wired Device tab select Configure HART Polling
Select Yes if changes are required
Wired Device tab
DVC5000 Digital Valve Controller
FOR PRIMARY DEVICE INFORMATION:
Select PV, SV, TV, and QV
FOR SECONDARY DEVICE INFORMATION:
Select Device Status