DVC5000 Digital Valve Controller
May 2018
Command 50: Read Dynamic Variable Assignments
This command returns a list of four device variable codes taken from table DVC Device Variables which are returned in
Command 3.
Byte
Request
None
Data Bytes
0
1
Response
2
Data Bytes
3
Code
Command­
Specific
None
Response
Codes
Command 54: Read Device Variable Information
Used to identify each of the Device Variables in the range of IDs 0, 1, 2, 3, 4, 6, 9, 10, and 211. Responds with the
Sensor Serial Number, Sensor range Units, Sensor ranges, Damping Value, and Minimum Span of the selected
Variable. The Variable range values will be in the same units as the Variable Units.
Byte
Request Data
0
Bytes
0
1­3
4
Response
5­8
Data Bytes
9­12
13­16
17­20
Code
Command­
Specific
2
Response
Codes
20
Format
Description
UINT8
ID of variable returned as the first variable (PV) in Command #3
UINT8
ID of variable returned as the second variable (SV) in Command #3
UINT8
ID of variable returned as the third variable (TV) in Command #3
UINT8
ID of variable returned as the fourth variable (FV) in Command #3
Class
Description
Format
Description
Device Variable ID, this command is applicable to variables 0, 1, 2, 3, 4,
Enum
6, 9, 10, and 211. All others will return invalid selection
UINT8
Device Variable ID (see "Device Variables" table page 6)
Device Variable Sensor Serial Number, 24­bit number
(NOT USED ­ always zero)
UINT8
Device variable units code (see "Units Codes" table on page 6.)
Float
Device Variable Upper Range
Float
Device Variable Lower Range
Device Variable Damping Value,
Float
(NOT USED ­ always zero)
Float
Device Variable Minimum Span (NOT USED ­ always zero)
Class
Description
Invalid Selection
Instruction Manual Supplement
D103266X012