Published Data, used for the Gateway's OPC and Modbus outputs, falls into the following categories:
Field Device Identification Values:
Values that define the identity of the DVC5000. These include:
D MANUFACTURER (for "Fisher Controls" the value is "19")
D DEVICE_TYPE (for a DVC5000 the value is "2")
D DEVICE_REVISION
D HARDWARE_REVISION
D SOFTWARE_REVISION
D DEVICE_ID
D UNIVERSAL_REVISION (HART version)
D REQUEST_PREAMBLES
D RESPONSE_PREAMBLES
Variable information:
The Gateway receives updates concerning the DVC5000's four "Dynamic Variables". The information for any given
device variable is displayed by:
1. Dynamic Variable indicator ("PV", "SV", etc.)
2. The Device Variable ID number assigned to that Dynamic Variable
Analog Input
Aux Contact Status
Pressure
Travel
Milliamp Current
Dynamic Variable
Device Variable ID
PV
SV
TV
QV
0
1
2
3
245
DVC5000 Digital Valve Controller
Device Variable Name(s)
ANALOG_INPUT
OUTPUT_PRESSURE
TRAVEL
CURRENT
May 2018
25