SETUP Menu - Function Block Descriptions

Note: To view the SETUP Menu, ADVANCED view level must be selected.

Understanding the Function Block Description

Note: The "Range" for a parameter value is given in the Parameter Description Table on each

MMI Menu Maps

690+ Series Frequency Inverter
The following function
blocks show the parameter
information necessary for
programming the Inverter.
Input parameters are shown
on the left hand side, and
output parameters are shown
on the right hand side of the
block.
The diagrams assume that the
UK country code is selected
and that a 400V 5.5kW
Frame C power board is
fitted. This is reflected in the
values of certain parameters,
see "*" and "**" in the table
below.
Instance Name
Names the function block and MMI menu
Default Value
The default value of the unmodified macro, Macro 0
Input/Output
The name shown on ConfigEd Lite
Parameter Name
Tag Number
Unique identification used for communications
*
Parameters marked with "*" are set to a value depending upon the
"operating frequency" of the drive. Refer to Chapter 2: "Parameter
Specification" - Frequency Dependent Defaults; and the Installation
Product Manual, Chapter 5: "The Operator Station" - Changing the
Product Code (3-button reset).
**
Parameters marked with "**" are set to a value depending on the overall
"power build " of the Inverter indicated by the product code. Refer to
Chapter 2: "Parameter Specification" - Power Dependent Defaults; and the
Installation Product Manual: Chapter 2: "Understanding the Product
Code".
Function Block page. Ranges for outputs are given as "—.xx %", for example, indicating
an indeterminate integer for the value, to two decimal places.
The function block descriptions include an easy-find menu showing
the menu levels and titles encountered to find the appropriate menu
title, and the parameters contained in the menu(s).
Where there is more than one instance, i.e. ANALOG INPUT as
illustrated, the parameters shown will be for the last instance.
Programming Your Application
Output Parameter
Name
Default Value
100.00% – [ 14] SCALE
0.00% – [ 15] OFFSET
0..+10V – [ 13] TYPE
FALSE – [ 12] BREAK ENABLE
0.00% – [ 17] BREAK VALUE
Tag Number
Figure 1-2 Function Block Parameter Information
MMI Menu Map
1 QUICK SETUP
VIEW LEVEL
Instance Name
Analog Input 1
VALUE
[ 16] – 0.00%
BREAK
[ 18] – FALSE
Default Value
Input Parameter
Name
MMI Menu Map
1 SETUP
2 INPUTS & OUTPUTS
3 ANALOG INPUT
4 ANALOG INPUT 1
4 ANALOG INPUT 2
SCALE
OFFSET
TYPE
BREAK ENABLE
BREAK VALUE
VALUE
BREAK
1-5