Removing and replacing the UID-health module

This operation is performed after Support determines that the UID-health module is the source
of the issue and requests the module be replaced
WARNING!
1.
Unplug the power cables.
2.
Remove the I/O cables. See
3.
Remove the fan module(s) with the failed control card. See
fan module" (page 19)
4.
Remove enclosure from rack. See
5.
Pull up hood latch and remove enclosure cover.
6.
Disconnect the rear UID-Health module cable from the backplane.
7.
Remove the UID-Health module retaining screw (1).
8.
Slide out the UID-Health module (2) while guiding the cable through the enclosure.
WARNING!
The cable could become unusable.
9.
Replace the UID-Health module by sliding the cable through the slot in the enclosure.
10. Reconnect the UID-Health module cable to the backplane.
11. Fasten the UID-Health module using the retaining screw.
12. Replace enclosure cover and press hood latch down to latch.
13. Replace the enclosure in the rack. See
24
Removal and replacement procedures
Check to make sure data on the drives is backed up. Back up data if required
"Removing and replacing I/O Cables" (page 17)
The UID cable is adhered to the chassis. Care should be taken to remove it.
"Removing and replacing the enclosure" (page 22)
"Removing and replacing the enclosure" (page 22)
"Removing and replacing the