3 Troubleshooting

If the enclosure does not initialize

IMPORTANT:
A/C power is restored, except in the following cases:
If both power supplies are damaged.
If there is a single power supply in the system, and it is damaged.
1.
Ensure that power has been applied to the enclosure.
2.
Verify that the power LED is green.
3.
Verify that the power source is working:
a.
Verify that the power supplies are working by viewing the power supply LEDs. If
necessary, remove and reinstall the power supplies to verify that they are seated properly.
b.
Remove and inspect AC power cords from both power supplies and reconnect them.

Diagnostic steps

Is the enclosure front fault LED amber?

Answer
No
Yes
30
Troubleshooting
After a power failure, the system automatically returns to the On state when
Possible Reasons
System functioning properly.
Front Status and UID module
might not be inserted properly,
might have a damaged connector,
or might have failed.
Possible error condition exists.
Actions
No action required.
Be sure that the Front Status and
UID module is undamaged and is
fully seated.
Check rear fault LEDs to isolate
failed component.
Contact an authorized service
provider for assistance.